IX
Troubleshooting ]
- 217 -
HWE0803A
GB
1. Error
Code
Heat exchanger outlet temperature sensor (TH3) fault (Outdoor unit)
Discharge temperature sensor (TH4) fault (Outdoor unit)
Accumulator inlet temperature sensor (TH5) fault (Outdoor unit)
Heat exchanger inlet temperature sensor (TH6) fault (Outdoor unit)
Outside temperature sensor (TH7) fault (Outdoor unit)
2. Error definition and error detection method
When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection),
the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor.
When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit
stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within the normal
range.
When a short or an open is detected again (the third detection) after the previous restart of the outdoor unit, the outdoor unit
makes an error stop.
When a short or an open of the thermistor is detected just before the restart of the outdoor unit, the outdoor unit makes an
error stop, and the error code "5102", "5103", 5104", "5105", "5106"or "5107" will appear.
During 3-minute antirestart mode, preliminary errors will be displayed on the LED display.
A short or an open described above is not detected for 10 minutes after the compressor start, during defrost mode, or for 3
minutes after defrost mode.
3. Cause, check method and remedy
<Reference>
5103
5104
5105
5106
5107
Cause
Check method and remedy
(1)
Thermistor failure
Check thermistor resistance.
(2)
Pinched lead wire
Check for pinched lead wire.
(3)
Torn wire coating
Check for wire coating.
(4)
A pin on the male connector is missing or
contact failure
Check connector.
(5)
Disconnected wire
Check for wire.
(6)
Thermistor input circuit failure on the control
board
Check the intake temperature of the sensor with the LED
monitor.
When the temperature is far different from the actual temper-
ature, replace the control board.
TH3
TH4
TH5
TH6
TH7
Open detection
-40 C [ -40 F ] and below (130 k )
0 C [ 32 F ] and below (698 k )
-40 C [ -40 F ] and below (130 k )
-40 C [ -40 F ] and below (130 k )
-40 C [ -40 F ] and below (130 k )
Short detection
110 C [230 F ] and above (0.4 k )
240 C [464 F ] and above (0.57 k )
70 C [158 F ] and above (0.4 k )
70 C [158 F ] and above (1.14 k )
110 C [230 F ] and above (0.4 k )
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......