IX
Troubleshooting ]
- 281 -
HWE0803A
GB
(2) Judgment methods and possible failure mode
Malfunction
mode
Judgment method
Remedy
Microcomputer
driver circuit fail-
ure
Disconnect the control board connector and connect
the check LED as shown in the figure below.
resistance : 0.25W 1k
LED : DC15V 20mA or more
When the main power is turned on, the indoor unit cir-
cuit board outputs pulse signals to the indoor unit LEV
for 10 seconds.
If any of the LED remains lit or unlit, the drive circuit is
faulty.
When the drive circuit has a
problem, replace the control
board.
LEV mechanism
is locked
If the LEV is locked, the drive motor runs idle, and
makes a small clicking sound.
When the valve makes a closing and opening sound,
the valve has a problem.
Replace the LEV.
Disconnected or
short-circuited
LEV motor coil
Measure resistance between the coils (red - white, red
-orange, brown - yellow, brown - blue) using a tester.
They are normal if resistance is 150ohm
10%.
Replace the LEV coils.
Incomple sealing
(leak from the
valve)
When checking the refrigerant leak from the indoor
LEV, run the target indoor unit in the fan mode, and the
other indoor units in the cooling mode. Then, check the
liquid temperature (TH22) with the self-diagnosis LED.
When the unit is running in the fan mode, the LEV is ful-
ly closed, and the temperature detected by the thermis-
tor is not low. If there is a leak, however, the
temperature will be low. If the temperature is extremely
low compared with the inlet temperature displayed on
the remote controller, the LEV is not properly sealed,
however, if there is a little leak, it is not necessary to re-
place the LEV when there are no effects to other parts.
If there is a large amount of
leakage, replace the LEV.
Faulty wire con-
nections in the
connector or
faulty contact
1.
Check for loose pins on the connector and check
the colors of the lead wires visually
Check the continuity at the
points where an error occurs.
2.
Disconnect the control board's connector and
conduct a continuity check using a tester.
6
5
4
3
2
1
1 k
LED
Thermistor
(liquid piping
temperature detection)
Linear Expansion Valve
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......