IX
Troubleshooting ]
- 251 -
HWE0803A
GB
1. Error
Code
Address setting error
2. Error definition and error detection method
Erroneous setting of OC unit address
Erroneous setting of BC controller address
3. Cause, check method and remedy
1. Error
Code
Attribute setting error
2. Error definition and error detection method
7105
Error source
Cause
Check method and remedy
Outdoor unit
BC controller
Erroneous setting of OC unit address
The address of outdoor unit is not being set to 51 -
100.
The address of BC controller is not set to 51 - 100.
Check that the outdoor unit and BC controller
addresses are set to 00 or a number between
51 and 100.
If the outdoor unit address is out of the valid
range, reset the address with the power to the
outdoor unit turned off.
If the BC controller address is out of the valid
range, reset the address with the power to both
the outdoor unit and BC controller turned off.
7106
Error source
Cause
Check method and remedy
-
A remote controller for use with indoor
units, such as the MA remote controller, is
connected to the OA processing unit whose
attribute is FU.
To operate the OA processing unit directly via a re-
mote controller for use with indoor units, such as the
MA remote controller, set the DIP SW 3-1 on the OA
processing unit to ON.
SW3-1
OFF
ON
Interlocked operation
with the indoor unit
Operation Method
Direct operation via the
MA remote controller
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......