VIII
Test Run Mode ]
- 169 -
HWE0803A
GB
Operation
Outdoor unit model
PURY-P192TSHMU-A
PURY-P96THMU-A
PURY-P96THMU-A
Model name of BC controller
CMB-P108NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/- [95°F/-]
Indoor unit
No. of connected units
Unit
6
No. of units in operation
6
Model
-
30/30/30/30/36/36
Piping
Main pipe
m
[ft]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
Total pipe length
65 [213-1/4"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
42.4 [93]
Outdoor
unit
Electric current
A
47.5
Voltage
V
230
Compressor frequency
Hz
65
65
LEV open-
ing
Indoor unit
Pulse
230/230/230/230/275/275
BC controller (1/2/3)
2000/2000/270
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.66/0.93
[385/134]
2.66/0.93
[385/134]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.59/2.59
[375/375]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
85 [185]
85 [185]
Heat exchanger outlet
(TH3)
39 [102]
39 [102]
Accumulator inlet
8 [46]
8 [46]
Accumulator outlet
8 [46]
8 [46]
Compressor inlet
19 [66]
19 [66]
Compressor shell bottom
42 [108]
40 [104]
Indoor unit
LEV inlet
19 [66]
Heat exchanger inlet
6 [43]
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......