II
Restrictions ]
- 17 -
HWE0803A
GB
II
Restrictions
[1] System configuration
1. Table
of
compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor
units
Composing units
Maximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
72
-
-
36 - 108
18
P06 - P96 models
R410A series indoor units
96
-
-
48 - 144
24
120
-
-
60 - 180
30
144
72
72
72 - 216
36
168
96
72
84 - 252
42
192
96
96
96 - 288
48
216
120
96
108 - 324
50
240
120
120
120 - 360
50