1. Error
Code
IPM error (Detail code 101)
2. Error definition and error detection method
In the case of 4250
Overcurrent is detected by the overcurrent detection resistor (RSH) on the INV board.
In the case of 4255
IPM error signal is detected.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 301)
4250
4255
(YHMU-A)
Cause
Check method and remedy
(1)
Inverter output related
Refer to IX [4] -7- (2) [1] - [4].(page 303)
Check the IGBT module resistance value of the INV board, if no
problems are found.
(Refer to the Trouble shooting for IGBT module)
Cause
Check method and remedy
(1)
Fan motor abnormality
Refer to IX [4] -7- (2) [5].(page 304)
(2)
Fan board failure
Refer to IX [4] -7- (2) [6].(page 304)