VII
Control ]
- 128 -
HWE0803A
GB
2) PURY-P96, P120THMU-A
All are set to OFF at factory shipment. Unless otherwise specified, set the switch to OFF where indicated by "-," which may
be set to a certain setting for a reason.
Leave SW1-1 to OFF during normal operation. If it is set to ON, errors cannot be detected and the unit may be damaged.
Switch
Function
Function according to switch
setting
Switch setting timing
OFF
ON
OFF
ON
SW1
1
Enabling/disabling the following error
detection functions;
ACCT/DCCT sensor failure
(5301 Detail No. 115, 116)
ACCT/DCCT sensor circuit failure
(5301 Detail No.117,118)
IPM open/Disconnected CNCT2
(5301 Detail No. 119)
Detection of erroneous wiring
(5301 Detail No.120)
Error detec-
tion enabled
Error detec-
tion disable
(No load op-
eration is pos-
sible.)
Anytime after power on
2
-
- - - -
3
-
- - - -
4
-
- - - -
5
-
- - - -
6
-
- - - -