[
IX
Troubleshooting ]
- 210 -
HWE0803A
GB
1. Error
Code
IPM error (Detail code 101)
2. Error definition and error detection method
In the case of 4250
P72 model
Overcurrent is detected by the overcurrent detection resistor (RSH) on the INVboard.
P96 and P120 models
IPM error signal is detected.
In the case of 4255
IPM error signal is detected.
3. Cause, check method and remedy
In the case of 4250
P72 model
P96 and P120 models
In the case of 4255
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 293)
4250
4255
(THMU-A)
Cause
Check method and remedy
(1)
Inverter output related
Refer to IX [4] -7- (2) [1] - [4].(page 295)
Cause
Check method and remedy
(1)
Inverter output related
Refer to IX [4] -7- (2) [1] - [4].(page 295)
(2)
Same as 4230 error
Same as 4230 error
Cause
Check method and remedy
(1)
Fan motor abnormality
Refer to IX [4] -7- (2) [5].(page 296)
(2)
Fan board failure
Refer to IX [4] -7- (2) [6].(page 296)
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......