VIII
Test Run Mode ]
- 165 -
HWE0803A
GB
(2) Heating only operation
Operation
Outdoor unit model
PURY-P72THMU-A
PURY-P96THMU-A
Model name of BC controller
CMB-P104NU-G
CMB-P104NU-G
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/-
[70°F/-]
21.1°C/-
[70°F/-]
Outdoor
8.3°C/6.1°C
[47°F/43°F]
8.3°C/6.1°C
[47°F/43°F]
Indoor unit
No. of connected units
Unit
3
2
No. of units in operation
3
2
Model
-
24/24/24
48/48
Piping
Main pipe
m
[ft]
5 [16-3/8"]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
10 [32-3/4"]
Total pipe length
35 [114-13/16"]
25 [82]
Fan speed
-
Hi
Hi
Amount of refrigerant
kg
[lbs-oz]
19.1 [42]
21.3 [47]
Outdoor
unit
Electric current
A
16.8
24.1
Voltage
V
230
230
Compressor frequency
Hz
48
71
LEV open-
ing
Indoor unit
Pulse
205/203/200
406/406
BC controller (1/2/3)
110/-/520
110/-/590
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.61/0.69
[378/100]
2.67/0.68
[387/98]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.54/2.22
[368/321]
2.63/2.31
[381/335]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
69 [156]
80 [176]
Heat exchanger outlet
(TH6)
0 [32]
0 [32]
Accumulator inlet
1 [34]
-2 [28]
Accumulator outlet
1 [34]
-3 [27]
Compressor inlet
1 [34]
-3 [27]
Compressor shell bottom
40 [104]
40 [104]
Indoor unit
LEV inlet
30 [86]
38 [100]
Heat exchanger inlet
63 [145]
70 [158]
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......