IX
Troubleshooting ]
- 218 -
HWE0803A
GB
1. Error
Code
Heatsink temperature sensor (THHS) fault (Detail code 01)
2. Error definition and error detection method
When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy
P72 model
P96 and P120 models
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 293)
1. Error
Code
Heatsink temperature sensor (THHS) fault (Detail code 01)
2. Error definition and error detection method
When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 301)
5110
(THMU-A)
Cause
Check method and remedy
(1)
INV board failure
If the problem recurs when the unit is put into operation, replace
the INV board.
Cause
Check method and remedy
(1)
THHS sensor failure
Check the THHS sensor reading on the LED monitor.
Replace the sensor if it reads below - 30°C[ -22°F] or above
150°C[302°F].
(2)
Contact failure
Check the connector connection (CNTH) on the INV board.
5110
(YHMU-A)
Cause
Check method and remedy
(1)
INV board failure
If the problem recurs when the unit is put into operation, replace
the INV board.
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......