VII
Control ]
- 137 -
HWE0803A
GB
(3) Outdoor unit heat exchanger capacity control patterns
Model
Operation
mode
Operation
patterns
Solenoid valve
SV4a
SV4b
SV4c
SV4d
SV5c
P72 model
Cooling-
only
Cooling-
main
1
OFF
OFF
-
ON
ON
2
OFF
OFF
-
OFF
ON
3
OFF
ON
-
OFF
ON
4
ON
OFF
-
OFF
ON
5
ON
ON
-
OFF
OFF
Heating-
only
1
ON
ON
-
OFF
OFF
Heating-
main
1
ON
ON
-
ON
OFF
2
ON
ON
-
OFF
OFF
Defrost
1
ON
ON
-
OFF
OFF
P96, P120 models
Cooling-
only
Cooling-
main
1
OFF
OFF
OFF
ON
ON
2
OFF
OFF
OFF
OFF
ON
3
OFF
OFF
ON
OFF
ON
4
OFF
ON
ON
OFF
ON
5
ON
ON
ON
OFF
OFF
Heating-
only
1
ON
ON
ON
OFF
OFF
Heating-
main
1
ON
ON
ON
ON
OFF
2
ON
ON
ON
OFF
OFF
Defrost
1
ON
ON
ON
OFF
OFF