VII
Control ]
- 135 -
HWE0803A
GB
-7- Defrost Operation Control
(1) Starting the defrost operation
The defrost cycle starts when the pipe temperature (TH6), in the following table, or below has continuously been detected for
3 minutes after the integrated compressor operation time of 50 minutes have passed.
If 10 minutes have passed since compressor start-up or since the completion of defrost operation, forced defrost operation
will start by turning on the forced defrost switch (DIP SW2-7).
Even if the defrost prohibit timer is set to 90 minutes, the actual defrost prohibit time for the next operation will be 50 minutes
if defrosting took 12 minutes.
In the multiple-outdoor-unit system, all of the outdoor units that are in operation go into the defrost mode simultaneously. The
unit(s) that is stopped at the time defrost operation starts remains stopped.
(2) Defrost operation
Model
TH6
SW3 - 3 OFF
SW3 - 3 ON
P72 model
- 10°C [14°F]
- 5°C [23°F]
P96 model
- 8°C [18°F]
- 5°C [23°F]
P120 model
- 8°C [18°F]
- 5°C [23°F]
Outdoou unit
Compressor frequency
Model
Compressor frequency
P72 model
60 Hz
P96 model
65 Hz
P120 model
65 Hz
Outdoor unit fan
Stopped
SV1a
ON (open)
SV2
ON (open)
SV5b
ON (open)
21S4a OFF
SV9
OFF (closed)
BC controller
LEV1
G type: 4000, GA type: 6000
LEV3
G type: 1000, GA type: 2000
GB, HB type: 60 (full closed)
SVM1
ON
SVM2
OFF
SV
B
OFF
SV
A
Ports that are connected to the indoor units in cooling Thermo-ON
Other ports : OFF
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......