6 FUNCTIONAL SAFETY
6.4 Safety sub-function
387
6
At alarm occurrence
This function displays an alarm and warning when an error occurs during operation. When an alarm and warning occur, refer
to the following manual and take the appropriate action.
MR-J5 User's Manual (Troubleshooting)
Outline
■
Stop methods
The following stop methods are available when functional safety is used.
For STO/DB, SS1/EDB, and SS1/SD, the STO state continues until the power is turned on again or the alarm is reset.
■
Safety sub-function stopped
If a serious error is detected, the safety sub-function stops. When the function stops, output devices output OFF.
■
Alarm reset
After the cause of the alarm is removed, the alarm can be cleared with one of the following methods.
• Alarm reset
• Communication reset
• Power cycling
Stop methods
Explanation
DB
Stops with dynamic brake (for a servo amplifier without the dynamic brake, the servo motor coasts).
EDB
The time constant
τ
for the electronic dynamic brake will be shorter than that of the normal dynamic brake. Therefore,
the coasting distance will be shorter than that of a normal dynamic brake.
SD
Performs forced stop deceleration.
STO/DB
Stops with dynamic brake by activating the STO function. For the operation sequence of this stop method, refer to the
following.
SS1/EDB
Stops with electronic dynamic brake by activating the SS1 function. For the operation sequence of this stop method,
refer to the following.
SS1/SD
Activates the SS1 function. Performs forced stop deceleration. For the operation sequence of this stop method, refer
to the following.