3 BASIC FUNCTION
3.11 In-position range setting
115
3
3.11
In-position range setting
The positioning completion status can be checked with INP (in-position). When the number of droop pulses falls within or less
than the range set in servo parameters, INP (in-position) turns on. In addition, the range unit for the in-position and the
conditions to turn on the in-position can be changed with servo parameters.
• INP is always off in the velocity mode, torque mode, and continuous operation to torque control mode.
Precautions
• If the value of [Pr. PA10 In-position range] is set too large and the servo motor is operated at a low speed, INP may always
be turned on. In this case, lower the setting value until the in-position signal stops being outputted.
• After the in-position has fallen to within or below the range, the in-position may turn on and off repeatedly if the droop
pulses exceed the in-position range due to overshoot, vibration, or oscillation. In that case, take actions such as adjusting
the gain and reviewing the operation pattern.
In the super trace control, droop pulses are near 0 during the servo motor control. Thus, the INP (In-position) signal may
remain on. To prevent the INP (In-position) signal from remaining on, set the servo parameters as follows.
[G] [WG]: [Pr. PD13.2 INP output signal ON condition selection] = "1" (Within the in-position range and at the completion of
command output)
[A]: [Pr. PD31.2 INP output signal ON condition selection] = "1" (Within the in-position range and at the completion of
command output)
ON
OFF
ON
OFF
Servo-on command
Occurring
Alarm
Not occurring
Command pulse frequency
Droop pulses
[Pr. PA10 In-position range]
INP (In-position)