6 OPTIONS AND PERIPHERAL EQUIPMENT
6.10 Molded-case circuit breakers, fuses, magnetic contactors
For control circuit power supply
When the wiring for the control circuit power supply (L11/L21) is thinner than that for the main circuit power supply (L1/L2/L3),
install an overcurrent protection device (molded-case circuit breaker, fuse, etc.) to protect the branch circuit.
■
200 V class
*1 To comply with the IEC/EN/UL/CSA standards, refer to the MR-J5 Safety Instructions and Precautions for AC Servos (IB(NA)-0300391)
for selection of molded-case circuit breakers and fuses.
■
400 V class
*1 To comply with the IEC/EN/UL/CSA standards, refer to the MR-J5 Safety Instructions and Precautions for AC Servos (IB(NA)-0300391)
for selection of molded-case circuit breakers and fuses.
Servo amplifier
Molded-case circuit breaker
Fuse (Class T)
Fuse (Class K5)
Frame, rated
current
Voltage AC [V]
Current [A]
Voltage AC [V]
Current [A]
Voltage AC [V]
MR-J5-10_
30 A frame 5 A
240
1
300
1
250
MR-J5-20_
MR-J5-40_
MR-J5-60_
MR-J5-70_
MR-J5-100_
MR-J5-200_
MR-J5-350_
MR-J5-500_
MR-J5-700_
MR-J5W2-22G_
MR-J5W2-44G_
MR-J5W2-77G_
MR-J5W2-1010G_
MR-J5W3-222G_
MR-J5W3-444G_
Servo amplifier
Molded-case circuit breaker
Fuse (Class T)
Fuse (Class K5)
Frame, rated
current
Voltage AC [V]
Current [A]
Voltage AC [V]
Current [A]
Voltage AC [V]
MR-J5-60_4_
30 A frame 5 A
480
1
600
1
600
MR-J5-100_4_
MR-J5-200_4_
MR-J5-350_4_