6 OPTIONS AND PERIPHERAL EQUIPMENT
6.10 Molded-case circuit breakers, fuses, magnetic contactors
221
6
For main circuit power supply [WG]
■
MR-J5W2-_G_
*1 To comply with the IEC/EN/UL/CSA standards, refer to the MR-J5 Safety Instructions and Precautions for AC Servos (IB(NA)-0300391)
for selection of molded-case circuit breakers and fuses.
*2 Use the magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of
80 ms or less.
*3 The molded-case circuit breaker is the same regardless of whether a power factor improving AC reactor is used.
*4 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
■
MR-J5W3-_G_
*1 To comply with the IEC/EN/UL/CSA standards, refer to the MR-J5 Safety Instructions and Precautions for AC Servos (IB(NA)-0300391)
for selection of molded-case circuit breakers and fuses.
*2 Use the magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of
80 ms or less.
*3 The molded-case circuit breaker is the same regardless of whether a power factor improving AC reactor is used.
*4 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
A motor circuit breaker (Type E combination motor controller) can also be used instead of a molded-case circuit breaker.
Use the motor circuit breaker (Type E combination motor controller) with the line side terminal adapter UT-CV3 and the short-
circuit indicator unit UT-TU.
Total output
of rotary
servo motors
Total
continuous
thrust of
linear servo
motors
Total output
of direct drive
motors
Molded-case circuit breaker
Fuse
Magnetic
contactor
Frame, rated
current
Voltage
AC [V]
Class
Current
[A]
Voltage
AC [V]
300 W or less
30 to 125 A frame 5 A
240
T
15
300
S-T10
From over 300 W
to 600 W
150 N or less
100 W or less
30 to 125 A frame 10 A
20
Over 600 W
1 kW or less
From over 150 N
to 300 N
From over 100 W
to 252 W
30 to 125 A frame 15 A
20
Over 1 kW
2 kW or less
From over 300 N
to 720 N
From over 252 W
to 838 W
30 to 125 A frame 20 A
30
S-T21
Total output
of rotary
servo motors
Total
continuous
thrust of
linear servo
motors
Total output
of direct drive
motors
Molded-case circuit breaker
Fuse
Magnetic
contactor
Frame, rated
current
Voltage
AC [V]
Class
Current
[A]
Voltage
AC [V]
450 W or less
150 N or less
30 to 125 A frame 10 A
240
T
20
300
S-T10
From over 450 W
to 800 W
From over 150 N
to 300 N
252 W or less
30 to 125 A frame 15 A
20
From over 800 W
to 1.5 kW
From over 300 N
to 450 N
From over 252 W
to 378 W
30 to 125 A frame 20 A
30
S-T21
Servo amplifier
Rated input voltage
AC [V]
Input phase
Motor circuit breaker (Type E combination motor
controller)
SCCR [kA]
Model
Rated voltage
AC [V]
Rated current
[A] (heater
design)
MR-J5W2-22G_
200 to 240
3-phase
MMP-T32
240
6.3
50
MR-J5W2-44G_
8
MR-J5W2-77G_
13
MR-J5W2-1010G_
18
MR-J5W3-222G_
8
MR-J5W3-444G_
13
Summary of Contents for MELSERVO-J5 MR-J5-G Series