6 OPTIONS AND PERIPHERAL EQUIPMENT
6.10 Molded-case circuit breakers, fuses, magnetic contactors
227
6
Related supplementary information
■
Permissible current of wire
The following table shows permissible currents of wire based on Table 28.1 of UL 508A and Table 40.3 of UL 508C.
The permissible current values listed in this table are for when the number of wires bundled is three or less. When the number
of wires bundled is four to six, the permissible current values are 80 % of the values in the table.
• Permissible currents of copper wire (insulated conductor)
■
Rated input current of servo amplifier
The following table shows the 3-phase rated input currents and maximum wire sizes for the MR-J5 series.
• 3-phase rated input currents, inrush currents, and maximum wire sizes for servo amplifiers
Wire size
60 °C (140 °F)
75 °C (167 °F)
AWG
Actual cross-sectional
area [mm
2
]
Nominal cross-
sectional area [mm
2
]
[A]
[A]
14
2.1
2
15
15
12
3.3
3.5
20
20
10
5.3
5.5
30
30
8
8.4
8
40
50
6
13.3
14
55
65
4
21.2
22
70
85
2
33.6
38
95
115
1
42.4
110
130
Model
Input current [A]
Inrush current [A]
Maximum AWG
MR-J5-10_
0.9
17
14
MR-J5-20_
1.5
17
14
MR-J5-40_
2.6
17
14
MR-J5-60_
3.2
17
14
MR-J5-70_
3.8
17
14
MR-J5-100_
5
17
14
MR-J5-200_
10.5
24
14
MR-J5-350_
16
85
12
MR-J5-500_
21.7
42
10
MR-J5-700_
28.9
85
8
MR-J5W2-22G_
2.9
23
14
MR-J5W2-44G_
5.2
23
14
MR-J5W3-222G_
4.3
23
14
MR-J5W3-444G_
7.8
23
14
MR-J5W2-77G_
7.5
36
14
MR-J5W2-1010G_
9.8
36
14
MR-J5-60_4_
1.4
16
14
MR-J5-100_4_
2.5
16
14
MR-J5-200_4_
5.1
22
14
MR-J5-350_4_
7.9
72
14