6 OPTIONS AND PERIPHERAL EQUIPMENT
6.15 Earth-leakage current breaker
249
6
MR-J5W_-_G_
Rated sensitivity current
≥
10 • {Ig1 + Ign + Iga + K • (Ig2 (A-axis) + Igm (A-axis) + Ig2 (B-axis) + Igm (B-axis) + Ig2 (C-axis) +
Igm (C-axis))} [mA] . . . (6.2)
Ig1: Leakage current on the electric channel from the earth-leakage current breaker to the input terminals of the servo
amplifier
Page 250 Example of leakage current (Ig1, Ig2) per km of CV cable run in metal conduit
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the servo motor
Page 250 Example of leakage current (Ig1, Ig2) per km of CV cable run in metal conduit
Ign: Leakage current when a filter is connected to the input side (4.4 mA per one FR-BIF(-H))
Iga: Servo amplifier leakage current
Page 250 Servo amplifier leakage current example (Iga)
Igm: Servo motor leakage current
Page 250 Servo motor leakage current example (Igm)
Earth-leakage current breaker
K
Type
Mitsubishi Electric products
Models provided with harmonic and surge reduction
techniques
NV-SP
NV-SW
NV-CP
NV-CW
NV-HW
1
General models
BV-C1
NFB
NV-L
3
Ign
Ig1
Iga
Ig2
Igm
Ig2
Igm
Ig2
Igm
M
NV
M
M
Cable
A-axis
Cable
Noise filter
Cable
Servo
amplifier
B-axis
Cable
C-axis
Summary of Contents for MELSERVO-J5 MR-J5-G Series
Page 2: ......
Page 473: ...12 USING A FULLY CLOSED LOOP SYSTEM 12 7 Absolute position detection system 471 12 MEMO ...
Page 477: ......