86
Frequency setting by external terminals
4.6.3
Input compensation of multi-speed and remote setting (Pr. 28)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
(Refer to page 173)
By inputting the frequency setting compensation signal (terminal 1, 2), the speed (frequency) can be
compensated for relative to the multi-speed setting or the speed setting by remote setting function.
Parameter
Number
Name
Initial Value
Setting Range
Description
28
Multi-speed input
compensation selection
0
0
Without compensation
1
With compensation
REMARKS
Select the compensation input voltage (0 to
r
5V, 0 to
r
10V) and used terminal (terminal 1, 2) using
Pr. 73 Analog input
selection
.
i
Parameters referred to
i
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239 (multi-speed operation)
Refer to page 82
Pr. 73 Analog input selection
Refer to page 155
Pr. 59 Remote function selection
Refer to page 87