61
Param
e
te
r
List
Parameter list
4
PA
R
A
M
E
T
E
R
S
P
ow
er
fa
ilu
re
st
op
261
Power failure stop selection
0, 1, 2, 21, 22
1
0
140
262
Subtracted frequency at deceleration
start
0 to 20Hz
0.01Hz
3Hz
140
263
Subtraction starting frequency
0 to 120Hz, 9999
0.01Hz
50Hz
140
264
Power-failure deceleration time 1
0 to 3600/ 360s
0.1/0.01s
5s
140
265
Power-failure deceleration time 2
0 to 3600/ 360s,
9999
0.1/0.01s
9999
140
266
Power failure deceleration time
switchover frequency
0 to 400Hz
0.01Hz
50Hz
140
267
Terminal 4 input selection
0, 1, 2
1
0
155
268
Monitor decimal digits selection
0, 1, 9999
1
9999
126
269
Parameter for manufacturer setting.
Do not set.
299
Rotation direction detection selection
at restarting
0, 1, 9999
1
9999
136
RS
-4
85
c
om
m
un
ic
at
io
n
331
RS-485 communication station
number
0 to 31(0 to 247)
1
0
194
332
RS-485 communication speed
3, 6, 12, 24,
48, 96, 192, 384
1
96
194
333
RS-485 communication stop bit
length
0, 1, 10, 11
1
1
194
334
RS-485 communication parity check
selection
0, 1, 2
1
2
194
335
RS-485 communication retry count
0 to 10, 9999
1
1
194
336
RS-485 communication check time
interval
0 to 999.8s, 9999
0.1s
0s
194
337
RS-485 communication waiting time
setting
0 to 150ms, 9999
1
9999
194
338
Communication operation command
source
0, 1
1
0
184
339
Communication speed command
source
0, 1, 2
1
0
184
340
Communication startup mode
selection
0, 1, 2, 10, 12
1
0
183
341
RS-485 communication CR/LF
selection
0, 1, 2
1
1
194
342
Communication EEPROM write
selection
0, 1
1
0
195
343
Communication error count
1
0
207
Re
mo
te
out
p
ut
495
Remote output selection
0, 1, 10, 11
1
0
123
496
Remote output data 1
0 to 4095
1
0
123
497
Remote output data 2
0 to 4095
1
0
123
Ma
in
te
na
n
ce
503
Maintenance timer
0 (1 to 9998)
1
0
254
504
Maintenance timer alarm output set
time
0 to 9998, 9999
1
9999
254
522
Output stop frequency
0 to 400Hz, 9999
0.01Hz
9999
108
539
Modbus-RTU communication check
time interval
0 to 999.8s, 9999
0.1s
9999
207
Co
m
m
un
ic
at
io
n
549
Protocol selection
0, 1
1
0
207
550
NET mode operation command
source selection
0, 1, 9999
1
9999
184
551
PU mode operation command source
selection
1, 2
1
2
184
Function Parameters
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Summary of Contents for F700
Page 327: ...318 MEMO ...
Page 340: ...331 MEMO ...