59
Param
e
te
r
List
Parameter list
4
PA
R
A
M
E
T
E
R
S
A
ut
om
a
tic
re
st
a
rt
fu
nc
tio
ns
162
Automatic restart after instantaneous
power failure selection
0, 1, 10, 11
1
0
136
163
First cushion time for restart
0 to 20s
0.1s
0s
136
164
First cushion voltage for restart
0 to 100%
0.1%
0%
136
165
Stall prevention operation level for
restart
0 to 120%
0.1%
110%
136
Cu
rr
en
t
det
ec
tio
n
166
Output current detection signal
retention time
0 to 10s, 9999
0.1s
0.1s
121
167
Output current detection operation
selection
0, 1, 10, 11
1
0
121
168
Parameter for manufacturer setting.
Do not set.
169
Cu
mu
la
tiv
e
mo
ni
to
r
cl
e
ar
170
Watt-hour meter clear
0, 10, 9999
1
9999
126
171
Operation hour meter clear
0, 9999
1
9999
126
U
se
r
gr
ou
p
172
User group registered display/batch
clear
9999, (0 to 16)
1
0
173
173
User group registration
0 to 999, 9999
1
9999
173
174
User group clear
0 to 999, 9999
1
9999
173
In
p
ut
te
rm
in
a
l f
un
ct
io
n
as
si
gn
m
en
t
178
STF terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 60, 62, 64 to 67,
70 to 72, 9999
1
60
110
179
STR terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 61, 62, 64 to 67,
70 to 72, 9999
1
61
110
180
RL terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 62, 64 to 67, 70
to 72, 9999
1
0
110
181
RM terminal function selection
1
1
110
182
RH terminal function selection
1
2
110
183
RT terminal function selection
1
3
110
184
AU terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 62 to 67, 70 to
72, 9999
1
4
110
185
JOG terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 62, 64 to 67, 70
to 72, 9999
1
5
110
186
CS terminal function selection
1
6
110
187
MRS terminal function selection
1
24
110
188
STOP terminal function selection
1
25
110
189
RES terminal function selection
1
62
110
Function Parameters
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Summary of Contents for F700
Page 327: ...318 MEMO ...
Page 340: ...331 MEMO ...