91
Setting of acceleration/deceleration time
and acceleration/deceleration pattern
4
PA
R
A
M
E
T
E
R
S
(2) Deceleration time setting
(Pr.8, Pr.20)
Use
Pr. 8 Deceleration time
to set the deceleration time required to reach 0Hz from
Pr. 20 Acceleration/deceleration
reference frequency
.
Set the deceleration time according to the following formula.
(3) Change the setting range and increments of the acceleration/deceleration time
(Pr.21)
Use
Pr. 21
to set the acceleration/deceleration time and minimum setting range.
Setting
"
0
"
(initial value)......................0 to 3600s (minimum setting increments 0.1s)
Setting
"
1
"
...........................................0 to 360s (minimum setting increments 0.01s)
(4) Set multiple acceleration/deceleration time (RT signal,
Pr.44, Pr.45
)
Pr. 44
and
Pr. 45
are valid when the RT signal is on.
When "9999" is set in
Pr. 45
, the deceleration time becomes equal to the acceleration time
(Pr. 44)
.
Example) How to find the setting value for
Pr.8
when decreasing the
output frequency from the maximum frequency of 40Hz in 10s
with
Pr.20
= 120Hz and
Pr.10
= 3Hz.
CAUTION
Changing the
Pr. 21
setting changes the acceleration/deceleration time setting
(Pr. 7, Pr. 8, Pr. 16, Pr. 44, Pr. 45)
.
(The
Pr. 611
Acceleration time at a restart
setting is not affected.)
<Example>
When
Pr. 21
= "0", setting "5.0" s in
Pr. 7
and "1" in
Pr. 21
automatically changes the
Pr. 7
setting to "0.5" s.
CAUTION
In S-shaped acceleration/deceleration pattern A
(refer to page 93)
, the set time is the period required to reach the base
frequency set in
Pr.3 Base frequency
.
Acceleration/deceleration time formula when the set frequency is the base frequency or higher
The RT signal can be assigned to the input terminal using any of
Pr. 178 to Pr. 189 (Input terminal function selection)
. Changing
the terminal assignment using
Pr. 178 to Pr. 189 (input terminal function selection)
may affect the other functions. Make setting
after confirming the function of each terminal.
REMARKS
The RT signal acts as the second function selection signal and makes the other second function valid.
(Refer to page 113)
The RT signal is assigned to the RT terminal in the default setting. By setting "3" to any of
Pr. 178 to Pr. 189 (Input terminal
function selection)
, you can assign the RT signal to the other terminal.
If the
Pr. 20
setting is changed, the
Pr. 125 and Pr. 126 (frequency setting signal gain frequency)
settings do not change. Set
Pr.
125 and Pr. 126
to adjust the gains.
When the
Pr. 7, Pr. 8, Pr. 44 and Pr. 45
settings are 0.03s or less, the acceleration/deceleration time is 0.04s. At that time, set
Pr. 20
to "120Hz" or less.
If the acceleration/deceleration time is set, the actual motor acceleration/deceleration time cannot be made shorter than the
shortest acceleration/deceleration time determined by the mechanical system J (moment of inertia) and motor torque.
i
Parameters referred to
i
Pr. 3 Base frequency
Refer to page 78
Pr. 10 DC injection brake operation frequency
Refer to page 100
Pr. 29 Acceleration/deceleration pattern selection
Refer to page 93
Pr. 125, Pr. 126 (Frequency setting gain frequency)
Refer to page 162
Pr. 178 to Pr.189 (Input terminal function selection)
Refer to page 110
Deceleration
time setting
=
Pr.20
u
Deceleration time from maximum
operating frequency to stop.
Maximum operating
frequency -
Pr. 10
Pr.8
=
120Hz
u
10s
32.4s
40Hz - 3Hz
Guideline for acceleration/deceleration time when
Pr. 3 Base frequency
= 50Hz (0Hz to set frequency)
t =
4
u
T
u
f
2
+
5
T
T: Acceleration/deceleration time setting value(s)
f : Set frequency(Hz)
9
(Pr.3)
2
9
Frequency setting (Hz)
50
120
200
400
Acceleration/
deceleration time (s)
5
5
16
38
145
15
15
47
115
429
Summary of Contents for F700
Page 327: ...318 MEMO ...
Page 340: ...331 MEMO ...