55
Param
e
te
r
List
Parameter list
4
PA
R
A
M
E
T
E
R
S
4.2 Parameter list
4.2.1
Parameter list
In the initial setting, only the simple mode parameters are displayed.
Set
Pr. 160 User group read selection
as required.
Parameter
Name
Initial
Value
Setting
Range
Remarks
160
User group read
selection
9999
9999
Only the simple mode parameters can be displayed.
0
Simple mode and extended mode parameters can be
displayed.
1
Only the parameters registered in the user group can be
displayed.
REMARKS
The parameters marked
are the simple mode parameters.
The parameters marked with
in the table allow its setting to be changed during operation even if "0" (initial
value) is set in
Pr. 77 Parameter write selection
.
Refer to the appendix 2
(page 322)
for instruction codes for communication and availability of parameter clear, all clear, and
parameter copy of each parameter.
Function Parameters
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
B
as
ic
fu
n
ct
io
ns
0
Torque boost
0 to 30%
0.1%
6/4/3/2/
1.5/1%
67
1
Maximum frequency
0 to 120Hz
0.01Hz
120/60Hz
76
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
76
3
Base frequency
0 to 400Hz
0.01Hz
50Hz
78
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
50Hz
82
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
82
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
82
7
Acceleration time
0 to 3600/ 360s
0.1/0.01s
5s/15s
90
8
Deceleration time
0 to 3600/ 360s
0.1/0.01s
10s/30s
90
9
Electronic thermal O/L relay
0 to 500/0 to 3600A
0.01/0.1A
Rated
inverter
current
95
DC
in
je
ct
io
n
br
ake
10
DC injection brake operation
frequency
0 to 120Hz, 9999
0.01Hz
3Hz
100
11
DC injection brake operation time
0 to 10s, 8888
0.1s
0.5s
100
12
DC injection brake operation voltage
0 to 30%
0.1%
4/2/1%
100
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
92
14
Load pattern selection
0, 1
1
1
80
Jo
g
op
er
at
io
n
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
84
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
84
17
MRS input selection
0, 2
1
0
112
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120/60Hz
76
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
8888
78
Summary of Contents for F700
Page 327: ...318 MEMO ...
Page 340: ...331 MEMO ...