IX
Troubleshooting ]
- 223 -
HWE1113B
GB
Items to be checked
Phenomena
Remedy
[4]
Check whether
the inverter is
damaged.
(During com-
pressor opera-
tion)
Put the outdoor unit into oper-
ation.
Check the inverter output volt-
age after the inverter output
frequency has stabilized.
1)
Overcurrent-related problems oc-
cur immediately after compressor
startup.
Error code : 4250
Detail code : 101, 106, 107
a.
Check items [1] through [3]
for problems.
b.
Check that high and low
pressures are balanced.
c.
Check that no liquid refrig-
erant is present in the
compressor.
ĺ
Go to "d." when the
problem persists after
compressor startup was
repeated several times.
If normal operation is re-
stored, check the crank-
case heater for problems.
d.
Check that there is a pres-
sure difference between
high and low pressures af-
ter compressor startup.
ĺ
Check the high pressure
with LED monitor for
changes.
Replace the compressor if
there is no pressure differ-
ence. (the compressor
may be locked.)
2)
There is a voltage imbalance be-
tween the wires after the inverter
output voltage is stabilized.
Greater than the larger of the fol-
lowing values: imbalance of 5% or
5V
Replace the INV board if there
is a voltage imbalance.
Check the crankcase heater
for problems if there is no volt-
age imbalance.
ĺ
When the error occurred, liq-
uid refrigerant may have been
present in the compressor.
[5]
Check the fan
motor ground
fault or the
winding.
Remove the wire for the out-
door fan motor, and check the
fan motor megger and the
winding resistance.
1)
Fan motor megger failure
Failure when the megger is 1Mohm
or less.
Replace the fan motor.
2)
Fan motor disconnection
Standard: The winding resistance
is approximately several ohm.
(It varies depending on the temper-
ature, or while the inner thermo is
operating, it will be
ohm)
[6]
Check the fan
inverter board
failure.
(1)
Check the fan output wir-
ing.
Connector contact failure
Board side (CNINV)
Fan motor side
Connect the connector.
(2)
Check the connector
CNVDC connection.
Cnnector contact failure
Connect the connector.
(3)
Check the FAN board
failure.
1)
The voltage imbalance among
each motor wiring during operation
(The voltage imbalance is greater
than the larger of the values repre-
sented by 5% or 5V.)
Replace the FAN board.
2)
The same error occurs even after
the operation is restarted.
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...