VII
Control ]
- 90 -
HWE1113B
GB
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed
A setting of CN3D is required.(page 28)
4) Refer to "VII [2] Controlling the Outdoor Unit" -5- Defrost Operation Control.(page 99)
5) OS is described in this manual, however OS does not exist because only a single outdoor unit can be connected in an HVRF
system.
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SW3
1
Test run mode: en-
abled/disabled
SW3-2 disabled
SW3-2 enabled
Anytime after power on
A
-
2
Test run mode: ON/
OFF
Stops all ICs
Sends a test-run
signal to all IC
After power on and when
SW3-1 is on.
A
-
3
Defrost start temper-
ature
(Note 4)
-8°C [18°F]
-5°C [23°F]
Anytime after power on
B
B
4
Defrost end temper-
ature
(Note 4)
7°C [45°F]
12°C [54°F]
Anytime after power on
(except during defrost op-
eration)
B
B
5
-
-
-
-
-
-
6
Temperature unit
setting
Centigrade
Fahrenheit
Anytime after power on
C
C
7
Heating mode selec-
tion at low outside
temperature
Performance priori-
ty mode
COP priority mode
Anytime after power on
A
-
8
-
-
-
-
-
-
9
Model setting
(High static pressure
setting (outdoor))
Outdoor standard
static pressure
Outdoor high static
pressure
Before being energized
C
C
10
Model setting
(High static pressure
setting (outdoor))
High static pressure
60Pa
High static pressure
30Pa
Before being energized
C
C
SW4
1
Enable/disenable high
sensible operation
Normal operation
mode
High sensible heat
operation mode
Before being energized
A
-
2
-
-
-
-
-
-
3
-
-
-
-
-
-
4
Low-noise mode/
step demand switch-
ing
Low-noise mode
(Note 3)
Step demand mode Before being energized
C
C
5
-
-
-
-
-
-
6
Cumulative com-
pressor operation
time data deletion
Cumulative com-
pressor operation
time data is retained.
Cumulative com-
pressor operation
time data is deleted.
Anytime after power on
(when the unit is turned
on)
C
C
7
-
-
-
-
-
-
8
-
-
-
-
-
-
9
-
-
-
-
-
-
10
-
-
-
-
-
-
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...