IX
Troubleshooting ]
- 149 -
HWE1113B
GB
4115
1. Error
Code
Power supply signal sync error
2. Error definition and error detection method
The frequency cannot be determined when the power is switched on.
3. Cause, check method and remedy
4116
1. Error
Code
RPM error/Motor error
2. Error definition and error detection method
LOSSNAY
The motor keep running even if the power is OFF.
The thermal overload relay is ON. (Only for the three-phase model)
Indoor unit
If detected less than 180rpm or more than 2000rpm, the indoor unit will restart and keep running for 3 minutes.If detected
again, the display will appear.
3. Cause, check method and remedy
4115
Cause
Check method and remedy
(1)
Power supply error
Check the voltage of the power supply terminal
block (TB1).
(2)
Noise filter problem
Coil problem
Circuit board failure
Check the coil connections.
Check for coil burnout.
Confirm that the voltage at the CN3 connector is
198 V or above.
(3)
Faulty wiring
Check fuse F01 on the control board.
(4)
Wiring failure
Between noise filter CN3 and noise filter CN2 and con-
trol board CNAC
Confirm that the voltage at the control board con-
nector CNAC is 198 V or above.
(5)
Control board failure
If none of the items described above is applicable,
and if the trouble reappears even after the power is
switched on again, replace the control board.
4116
Cause
Check method and remedy
(1)
Board failure
Replace the board.
(2)
Motor malfunction
Check for the motor and the solenoid switch.
(3)
Solenoid switch malfunction
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...