VII
Control ]
- 101 -
HWE1113B
GB
(4) Recovering from Defrost
The setting of the dip switch 3-10 determines the defrost method (bypass defrost or heat recovery defrost).
As shown in the following flow chart, the bypass defrost may be performed during the heat recovery defrost depending on the
operation status.
Heating-only or
Heating-main
Receiving
"Defrost" signal
from OC
No
Yes
Bypass defrost
ON
OFF
HBC Dip switch
SW3-10
High pressure heat recovery defrost:
LEV1, 2 = 3000
LEV3 = 3000
Pump = Always in operation
Indoor unit FCV during Thermo-ON = Fully open
No
No
No
No
Lower the frequency,
count the No. of freezing.
Freezing is
suspected.
No. of freezing
< 3 times
Yes
Yes
Yes
Receiving
"Defrost" signal
from OC
Recovering from Defrost
Yes
Water temp. < 20ºC
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...