[
VII
Control ]
- 111 -
HWE1113B
GB
[4] Operation Flow Chart
1. Mode determination flowchart
(1) Indoor unit (cooling, heating, dry, fan mode)
Start
Remote controller
display lit off
Error mode
Error stop
Error display
Self-holding of
protection function
Error command
to outdoor unit
Indoor unit
LEV fully closed.
Refer to 2-(1) for
cooling operation.
Refer to 2-(2) for
heating operation.
Refer to 2-(3) for
dry operation.
Prohibition
Prohibition
Prohibition
Dry display
Heating display
Cooling display
Dry mode
Heating mode
Fan mode
Fan display
Fan operations
Operation
mode
Cooling mode
Prohibition
"Blinking display on
the remote controller"
FAN stop
Breaker
turned on
Operation SW
turned on
Auxiliary heater
ON
Drain pump
ON
3-minute drain
pump ON
NO
NO
NO
NO
NO
NO
NO
NO
NO
*Note 1
*Note 1
*Note 2
*Note 3
*Note 3
*Note 3
1. Protection function
self-holding cancelled.
2. HBC controller FCV fully closed.
1. Auxiliary heater OFF
2. Low fan speed for
1 minute
YES
YES
YES
YES
YES
YES
YES
YES
Normal operation
Error
Stop
1
Prohibition
Auto COOL/HEAT
display
Automatic
cooling/heating mode
*Note 3
YES
Auto
cooling/heating mode
1
1
*Note 1. HBC controller FCV fully closed : Opening 1600.
*Note 2. The system may go into the error mode on either the indoor unit side or the HBC controller or outdoor unit side.
If some of the indoor units are experiencing a problem, only those indoor units that are experiencing the problem
will stop. If the HBC controller or the outdoor unit is experiencing a problem, all the connected units will stop.
*Note 3. If multiple indoor units are connected to a port and there is a discrepancy in the operation mode between the
indoor unit and the port, the operation will be prohibited. (Operation mode blinks on the remote controller, the
Fan stops, HBC controller FCV becomes fully closed.)
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...