IX
Troubleshooting ]
- 144 -
HWE1113B
GB
2512
1. Error
Code
3-way valve/Water flow rate control valve fault
2. Error definition and error detection method
Limit signal that is output from 3-way valve/water flow rate control valve is not detected or is not reset after it is detected.
3. Cause, check method and remedy
2512
Cause
Check method and remedy
(1)
Loose connectors, wiring fault
When the LEDs on the control board (MV1a-MV1h, MV2a-
MV2h, and FCV3a-FCV3h) are lit, check the 3-way valves/
water flow rate control valves whose LED is lit for loose
connectors, wiring fault, and proper operation. When the
LEDs described above are not lit, check all the 3-way
valves/water flow rate control valves for proper operation.
(2)
3-way valve/Water flow rate control valve fault
(3)
Control board fault
If no problems are found with the above items, replace the
control board.
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...