VI
Refrigerant Circuit ]
- 85 -
HWE1113B
GB
2. Indoor
Unit
Part
Name
Symbol
(functions)
Notes Usage
Specification Check
method
Thermis-
tor
TH1
(Suction air
temperature)
Indoor unit control (Thermo)
0°C [32°F]:15kohm
10°C [50°F] :9.7kohm
20°C [68°F]:6.4kohm
25°C [77°F] :5.3kohm
30°C [86°F] :4.3kohm
40°C [104°F] :3.1kohm
Resistance check
TH2
(Pipe temper-
ature from
HBC control-
ler)
Indoor unit control (Inlet water
temperature detection)
TH3
(Pipe temper-
ature to HBC
controller)
Indoor unit control (Outlet wa-
ter temperature detection)
Temperature
sensor (In-
door air tem-
perature)
Indoor unit control (Thermo)
1
273+t
R
0
=15k
R
0/80
=3460
Rt =
15exp{3460( - )}
1
273