IX
Troubleshooting ]
- 166 -
HWE1113B
GB
6600
1. Error
Code
Address overlaps
2. Error definition and error detection method
An error in which signals from more than one indoor units with the same address are received
The address and attribute that appear on the remote controller indicate the controller that detected the error.
3. Cause, check method and remedy
6601
1. Error
Code
Polarity setting error
2. Error definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
3. Cause, check method and remedy
6600
Cause
Check method and remedy
(1)
Two or more of the following have the same address:
Outdoor units, HBC controllers, indoor units, LOSS-
NAY units, controllers such as ME remote controllers.
<Example>
6600 "01" appears on the remote controller
Unit #01 detected the error.
Two or more units in the system have 01 as their ad-
dress.
Find the unit that has the same address as that of the error
source.
Once the unit is found, correct the address. Then, turn
off the outdoor units, indoor units, and LOSSNAY
units, keep them all turned off for at least five minutes,
and turn them back on.
When air conditioning units are operating normally despite
the address overlap error
Check the transmission wave shape and noise on the
transmission line.
See the section "Investigation of Transmission Wave
Shape/Noise."
(2)
Signals are distorted by the noise on the transmission
line.
6601
Cause
Check method and remedy
(1)
No voltage is applied to the M-NET transmission line
that AG-150A/GB-50ADA/PAC-YG50ECA/BAC-
HD150 are connected to.
Check if power is supplied to the M-NET transmission
line of the AG-150A/GB-50ADA/PAC-YG50ECA/BAC-
HD150, and correct any problem found.
(2)
M-NET transmission line to which AG-150A/GB-
50ADA/PAC-YG50ECA/BAC-HD150 are connected
is short-circuited.
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...