VII
Control ]
- 109 -
HWE1113B
GB
Bypass Control
-5- Bypass Control
Solenoid valves have two types: (SVM1) that bypass the high- and low- pressure sides; LEV (LEV3). They perform the fol-
lowing functions.
(1) Bypass solenoid valve (SVM1) (ON: open)
Plate heat exchanger contro
-6- Plate heat exchanger control
(1) Cooling-only Thermo-ON and Cooling-only test run
When three minutes have passed after the LEV operates with initial opening, the LEV opening is adjusted every 1 minute to
keep the amount of superheat before and after the plate heat exchanger constant.
(2) Heating-only Thermo-ON
When three minutes have passed after the LEV operates with initial opening, the LEV opening is adjusted every 1 minute to
keep the amount of subcool before and after the plate heat exchanger constant.
(3) Cooling-main/Heating-main Thermo-ON and Cooling-main/Heating-main refrigerant recovery
1) Periodic control for LEV1
The LEV opening is adjusted the same way as described in (2) Heating-only Thermo-ON and Heating-only refrigerant recov-
ery.
2) Periodic control for LEV2
To be fully open (3000)
Operation mode
SVM1
ON OFF
Cooling-only Thermo-ON
Always ON
Cooling-main Thermo-ON
Always OFF
Heating-only Thermo-ON
Always OFF
Heating-main Thermo-ON
Always OFF
Defrost
Always ON during heat recovery de-
frost
OFF except to perform heat recovery
defrost
Stop
Always OFF
Cooling-only Thermo-OFF
Always ON
Thermo-OFF (Heating-only, Mixture of
units in cooling and heating)
Always OFF
Cooling-only test run
Always ON
Test run for stop
Always ON
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...