II
Restrictions ]
- 45 -
HWE1113B
GB
[8] Restrictions on Pipe Length
1) All the indoor units that are connected to the same port must be in the same group and Thermo-ON/OFF operation simulta-
neously. For all the indoor units in the group, the room temperature needs to be monitored via the connected remote controller.
a
H,H'
h1
A
h2
Outdoor unit
HBC controller
B
d
c
Branch joint
Indoor
Indoor
Indoor
(WP15 - WP50 models)
Maximum of 3 units per port
Total capacity of WP80 or below
Unit: m [ft]
Operation
Pipe sections
Allowable length of pipes
Length
Total pipe length
A+B+a+c+d
No restrictions
Between outdoor unit and HBC controller
A
110 [360] or less
Between HBC controller and indoor unit
B+d
60 [196] or less
Height
difference
Between HBC controller and outdoor
units
H,H'
50 [164] or less
Between indoor unit and HBC controller
h1
15[49](10[32]) or less
Between indoor units
h2
15[49](10[32]) or less
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...