- 30 -
[
II
Restrictions ]
GB
HWE1113B
[5] An Example of a System to which an MA Remote Controller is connected
1. System with one outdoor unit (automatic address setup for both indoor and outdoor units)
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) When the number of the connected indoor units is as
shown in the table below, one or more transmission
boosters (sold separately) are required.
To connect two transmission boosters, connect them in
parallel. (Observe the maximum number of connectable
indoor units that are listed in the specifications for each
outdoor unit.)
4) Automatic address setup is not available if start-stop in-
put(CN32, CN51, CN41) is used for a group operation of
indoor units. Refer to "[5] 2. Manual address setup for
both indoor and outdoor units"(page 32)
5) To connect more than 2 LOSSNAY units to indoor units
in the same system, refer to "[5] 2. An example of a sys-
tem with one outdoor unit to which 2 or more LOSSNAY
units are connected".(page 32)
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2
[AWG16] or larger)
L1 +L2+L3+L4+L5
200m[656ft]
L1 +L2+L3+L11+L12+L13
200m[656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16])
m1
200m [656ft]
m2+m3
200m [656ft]
m4+m5
200m [656ft]
IC
TB5
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
S
TB15
1 2
00
IC
TB5
S
TB15
1 2
00
A1 B2
MA
A1 B2
MA
A1 B2
RC
LC
TB5
S
00
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
00
00
IC
TB5
S
TB15
1 2
00
A1 B2
MA
A1 B2
MA
A1 B2
MA
Group
Group
Group
Group
A1 B2
MA
m1
L11
m2
L4
L5
L12
L13
m3
m5
m4
Interlock operation with
the ventilation unit
*1. The figures above show a system to which two
outdoor units are connected, but only a single
outdoor unit can be connected in an HVRF
system.
*1
HB
00
OC
00
TB7
M1 M2
S
TB3
OS
00
TB7
M1 M2
M1 M2
M1 M2
S
TB3
TB02
M1 M2 S
L3
L1
L2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
Number of transmission
booster (sold separately) re-
quired
1 unit
2 units
When the P200 and P250 mod-
els are not included in the con-
nected indoor units
27 - 50 units
-
When the P200 and P250 mod-
els are included in the connect-
ed indoor units
21 - 39 units
40 - 50 units
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...