VII
Control ]
- 92 -
HWE1113B
GB
2. Function of the switch (Indoor unit)
(1) Dipswitches
1) SW1,3
2) SW2
SW3-1
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Very Low
Low
Preset speed
Preset speed
Preset speed
Stop
Stop
Stop
Stop
Switch setting
SW1-7 SW1-8
Heating
Cooling
Cooling-only/heat pump
Heat pump
Cooling-only
Heat pump
Fan speed during Thermo-OFF
Note 2. If both SW1-7 and SW1-8 are set to ON, the fan remains stopped during heating Thermo-OFF.
To prevent incorrect temperature detection due to a build-up of warm air around the indoor unit, use the built-in temperature sensor on the remote controller (SW1-1)
instead of the one on the indoor unit inlet thermistor.
Note 3. By setting SW3-1, SW1-7, and SW1-8 to a certain configuration, the fan can be set to remain stopped during cooling Thermo-OFF. See the table below for details.
Switch
Function
Function according to switch setting
OFF
ON
Switch setting timing
OFF
ON
Notes
SW1
SW3
1
2
3
4
5
6
7
8
9
10
9
10
1
2
3
4
5
6
7
8
Room temperature
detection position
Clogged filter detection
Filter check reminder time setting
Outside air intake
Remote display option
Humidifier control
Self-recovery after power failure
Fan speed setting for
Heating Thermo-OFF
Power source start-stop
Unit model selection
Louver
Vane
Vane swing function
-
Vane angle limit setting
for cooling operation
Heating 4°C [7.2°F] up
Raises supply air
temperature in heating mode
Indoor unit inlet
100h
Disabled
Fan output
2500h
Enabled
Thermo-ON signal
Built-in sensor on
the remote controller
Available
During heating operation
According to the
SW1-7 setting
Heat pump
Always on while in the heating mode
Fan speed setting for
Heating Thermo-OFF
Very Low
Low
Preset speed
Cooling only
Enabled
Disabled
Disabled
Enabled
Enabled
Not available
Available
Not available
Available
Not available
Not available
Available
OFF
ON
OFF
ON
-
-
Downblow B,C
Horizontal
While the unit is stopped
(Remote controller OFF)
Set to OFF on floor-standing
(PFFY) type units
Disabled
Precooling standby
Water inlet temp. ≥ 35°C
or 5 minutes have elapsed
after starting operation
Water inlet temp. ≥ 35°C
or 10 minutes have elapsed
after starting operation
Preheating standby end
conditions
-
-
-
Note 1. Settings in the shaded areas are factory settings.(Refer to the table below for the factory setting of the switches whose factory settings are not indicated by the shaded cells.)
Model
Capacity (model) code
SW2
setting
Note. The setting timing for SW2 is before power is turned on.
P20
4
P15
3
P25
5
P32
6
P40
8
P50
10
P63
13
P71
14
P80
16
P100
20
P125
25
P200
40
P250
50
P140
28
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
ON
OFF
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...