4. Switch functions <HBC controller> (Control board)
Switch Function
Function according to switch setting
Switch setting tim-
ing
OFF
ON
SW3
1 - 3
Model setting
R410A
-
Always leave this
switch to OFF.
4
-
-
-
-
5
SVM1 ON fixed
control
Not available
Available
Any time after be-
ing energized
6 - 7
Pressure sensor
backup
Error codes are not sent to
outdoor units
Error codes are sent to out-
door units.
Any time after be-
ing energized
8
-
-
-
-
9
-
-
-
-
10
Heat recovery de-
frost
Available
Not available
Before being ener-
gized
SW4
1
Test run air vent
mode before strain-
er processing
Not available
Available
Any time after be-
ing energized
2
Skipping the test
run air vent mode
Not available
Available
Any time after be-
ing energized
3
Test run air vent
mode after strainer
processing
Not available
Available
Any time after be-
ing energized
4
Forced termination
of a test run
Not available
Available
Any time after be-
ing energized
5
Water tightness
check
Not available
(When the switch is set from
ON to OFF, set the MV1,
MV2, and FCV to the speci-
fied opening for stoppage.)
Available
Two water pumps ON (output
30%) one minute after setting
MV1, MV2, and FCV on all
ports to 800, 800, and 0 re-
spectively.
Any time after be-
ing energized (only
when the control
mode is stopped)
6
Operation functions
of the 3-way valve
and water flow rate
control valve 1
Not available
MV1 (All ports) =0
MV2 (All ports) = 600
FCV (All ports)=1600
Any time after be-
ing energized
7
Operation functions
of the 3-way valve
and water flow rate
control valve 2
Not available
MV1 (All ports) 1600
MV2 (All ports) =0
FCV (All ports)=1600
Any time after be-
ing energized
8
-
-
-
-
9
-
-
-
-
10
-
-
-
-
SW5
1
Water supply SW
Not available
Available
Any time after be-
ing energized
2
Air vent SW
Not available
Available
Any time after be-
ing energized
3
-
-
-
-
4
Compatible with
brine 1
Refer to the Databook.
5
Compatible with
brine 2
6
-
-
-
-
7
-
-
-
-
8
-
-
-
-
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...