VI
Refrigerant Circuit ]
- 86 -
HWE1113B
GB
3. HBC
controller
Part name
Symbols
Notes
Usage
Specifications
Check method
Solenoid
valve
SVM1
Refriger-
ant side
Opens during the cooling mode
and defrost cycle
AC220-240V
Open when energized/
closed when de-energized
Continuity check
with a tester
4-way
valve
21S4Ma,b
Refriger-
ant side
Switches between heating and
cooling
AC220-240V
Open when energized/
closed when de-energized
Continuity check
with a tester
LEV
LEV1
Refriger-
ant side
Supplies refrigerant to HEX1a
and HEX1b
DC12V
Opening of a valve driven by
a stepping motor
0~3000 pulses
Refer to the sec-
tion "Continuity
Test with aTest-
er".
Continuity be-
tween white, red,
and orange.
Continuity be-
tween yellow,
brown, and blue.
LEV2
Refriger-
ant side
Supplies refrigerant to HEX2a
and HEX2b
LEV3
Refriger-
ant side
Subcool control
Thermistor TH11,12,
T13,14
Refriger-
ant side
1) Compressor frequency con-
trol
2) LEV opening adjustment
0°C[32°F] : 15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
TH15,16
Bypass superheat amount ad-
justment
TH31a~h
Water
side
Indoor unit circulating water con-
trol
TH32,33
Indoor unit circulating water con-
trol
TH34,35
Water pump error detection
TH36,37
Water pump suction water tem-
perature detection
Pressure
sensor
PS1
Refriger-
ant side
1) Detects high pressure
2) LEV controll
3-way
valve
MV1a~h
MV2a~h
*1
Water
side
Switches the water flow path de-
pending on the operation mode
DC12V
Opening of a valve driven by
a stepping motor
*2
Water flow
rate con-
trol valve
FCV3a~h
*1
Water
side
Temperature difference control
Controls the water flow to each
indoor unit
DC12V
Opening of a valve driven by
a stepping motor
*3
Pump
PUMP1,2
Water
side
Temperature difference control
Controls the water flow to each
indoor unit
Rated voltage DC268V
Specified voltage DC0-6V
Water
pressure
protection
valve
CPV1~7
Water
side
Trips when the internal pressure
in the water circuit rises
Operating pressure: 490
kPa
*1. The names of port "a" through "h" are corresponding to port 1 through 8.
*2. Valve opening is controlled with 0, 800,1600 pulses. In the Maintenance Tool, "0" indicates 0 pulse, "1" indicates 1600
pulses, and "2" indicates 800 pulses.
*3. For the degree of valve opening, "0" indicates fully open and "1600" indicates fully closed.
Yellow
White
Red
Orange
Brown Blue
M
R = 15k
0
R = 3460
R = 15
0/80
t
3460
273 t
1
273
1
exp
Pressure
0~4.15 MPa [601psi]
Vout 0.5~3.5V
0.071V/0.098 MPa [14psi]
Pressure [MPa]
=1.38 x Vout [V]-0.69
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
GND (Black)
Vout (White)
Vcc (DC5V) (Red)
Con-
nector
PS1
1
1 2 3
2
3
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...