[
IV
Remote Controller ]
- 65 -
HWE1113B
GB
IV
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers
There are two types of remote controllers: ME remote controller, which is connected on the indoor-outdoor transmission
line, and MA remote controller, which is connected to each indoor unit.
1. Comparison
of
functions and specifications between MA and ME remote controllers
2. Remote controller selection criteria
MA remote controller and ME remote controller have different functions and characteristics. Choose the one that better suits
the requirements of a given system. Use the following criteria as a reference.
Functions/specifications
MA remote controller
*1*2
*1. MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and wire-
less remote controller.
*2. Either the MA remote controller or the ME remote controller can be connected when a group operation of units in a sys-
tem with multiple outdoor units is conducted or when a system controller is connected.
ME remote controller
*2*3
*3. ME remote controller refers to ME remote controller and ME simple remote controller.
Remote controller address settings
Not required
Required
Indoor/outdoor unit address set-
tings
Not required (required only by a system
with one outdoor unit)
*4
*4. Depending on the system configuration, some systems with one outdoor unit may require address settings.
Required
Wiring method
Non-polarized 2-core cable
To perform a group operation, daisy-
chain the indoor units using non-polar-
ized 2-core cables.
Non-polarized 2-core cable
Remote controller connection
Connectable to any indoor unit in the
group
Connectable anywhere on the indoor-out-
door transmission line
Interlock with the ventilation unit
Each indoor unit can individually be in-
terlocked with a ventilation unit. (Set up
via remote controller in the group.)
Each indoor unit can individually be inter-
locked with a ventilation unit. (Set up via
remote controller.)
Changes to be made upon group-
ing change
MA remote controller wiring between in-
door units requires rewiring.
Either the indoor unit address and remote
controller address must both be changed,
or the registration information must be
changed via MELANS.
MA remote controller
*1*2
ME remote controller
*1*2
There is little likelihood of system expansion and group-
ing changes.
Grouping (floor plan) has been set at the time of instal-
lation.
There is a likelihood of centralized installation of remote
controllers, system expansion, and grouping changes.
Grouping (floor plan) has not been set at the time of in-
stallation.
To connect the remote controller directly to the OA pro-
cessing unit.
*1. ME remote controller and MA remote controller cannot both be connected to the same group of indoor units.
*2. A system controller must be connected to a system to which both MA remote controller and ME remote controller are con-
nected.
<System with MA remote controller>
<System with ME remote controllers>
MA remote controller
Outdoor unit
Indoor unit
BC controller
M-NET transmission line
(indoor/outdoor transmission line)
group
group
ME remote controller
Outdoor unit
Indoor unit
BC controller
M-NET transmission line
(indoor/outdoor transmission line)
group
group
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...