1. Error
Code
Connection information signal transmission/reception error
2. Error definition and error detection method
The given indoor unit is inoperable because it is not properly connected to the outdoor unit in the same system.
3. Error source, cause, check method and remedy
7111
1. Error
Code
Remote controller sensor fault
2. Error definition and error detection method
This error occurs when the temperature data is not sent although the remote controller sensor is specified.
3. Error source, cause, check method and remedy
7110
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Power to the transmission booster is cut off.
1)
Confirm that the power to the transmission
booster is not cut off by the booster being
connected to the switch on the indoor unit.
(The unit will not function properly unless the
transmission booster is turned on.)
(2)
Power resetting of the transmission booster
and outdoor unit.
->Reset the power to the outdoor unit.
(3)
Wiring failure between OC and OS
2)
Confirm that the TB3 on the OC and OS are
properly connected.
(4)
Broken wire between OC and OS.
3)
Check the model selection switch on the out-
door unit (Dipswitch SW5-7 on the control
board.).
(5)
The model selection switch (SW5-7) on the
outdoor unit is set to OFF. (Normally set to
ON)
7111
Error source
Cause
Check method and remedy
Indoor unit
OA process-
ing unit
The remote controller without the temperature
sensor (the wireless remote controller or the
ME compact remote controller (mounted
type)) is used and the remote controller sen-
sor for the indoor unit is specified. (SW1-1 is
ON.)
Replace the remote controller with the one
with built-in temperature sensor.
Summary of Contents for City Multi CMB-WP108V-G
Page 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Page 11: ... 2 HWE1113B GB ...
Page 27: ... I Read Before Servicing 18 HWE1113B GB ...
Page 29: ... 20 HWE1113B GB ...
Page 57: ... 48 HWE1113B GB ...
Page 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Page 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Page 73: ... 64 HWE1113B GB ...
Page 81: ... IV Remote Controller 72 HWE1113B GB ...
Page 83: ... 74 HWE1113B GB ...
Page 89: ... 80 HWE1113B GB ...
Page 97: ... 88 HWE1113B GB ...
Page 127: ... 118 HWE1113B GB ...
Page 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Page 137: ... 128 HWE1113B GB ...
Page 253: ... 244 HWE1113B GB ...