71
Par
a
meter
Li
st
Parameter list
4
BAC
net
M
S
/T
P pr
ot
oc
ol
726
Auto Baudrate/Max Master
0 to 255
1
255
727
Max Info Frames
1 to 255
1
1
728
Device instance number (Upper 3
digit)
0 to 419 (0 to 418)
1
0
729
Device instance number (Lower 4
digit)
0 to 9999 (0 to 4302)
1
0
PI
D
c
ont
ro
l
753
Second PID action selection
10, 11, 20, 21, 50, 51,
60, 61, 70, 71, 80, 81,
90, 91, 100, 101, 110,
111, 120, 121, 9999
1
9999
754
Second PID control automatic
switchover frequency
0 to 400Hz, 9999
0.01Hz
9999
755
Second PID action set point
0 to 100%, 9999
0.01%
9999
756
Second PID proportional band
0.1 to 1000%, 9999
0.1%
100%
757
Second PID integral time
0.1 to 3600s, 9999
0.1s
1s
758
Second PID differential time
0.01 to 10.00s, 9999
0.01s
9999
759
PID unit selection
0 to 43, 9999
1
9999
760
Pre-charge fault selection
0, 1
1
0
761
Pre-charge ending level
0 to 100%, 9999
0.1%
9999
762
Pre-charge ending time
0 to 3600s, 9999
0.1s
9999
763
Pre-charge upper detection level
0 to 100%, 9999
0.1%
9999
764
Pre-charge time limit
0 to 3600s, 9999
0.1s
9999
765
Second pre-charge fault selection
0, 1
1
0
766
Second pre-charge ending level
0 to 100%, 9999
0.1%
9999
767
Second pre-charge ending time
0 to 3600s, 9999
0.1s
9999
768
Second pre-charge upper detection
level
0 to 100%, 9999
0.1%
9999
769
Second pre-charge time limit
0 to 3600s, 9999
0.1s
9999
PU
774
PU/DU monitor selection 1
1 to 3, 5, 6, 8 to 14, 17,
20, 23 to 25, 40 to 42,
50 to 57, 67, 81 to 86,
100, 9999
1
9999
775
PU/DU monitor selection 2
776
PU/DU monitor selection 3
Function Parameters
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Summary of Contents for 700 Series
Page 11: ...MEMO ...
Page 23: ...12 MEMO ...
Page 341: ...330 MEMO ...
Page 365: ...354 MEMO ...
Page 379: ...368 MEMO ...
Page 397: ...386 MEMO ...
Page 414: ...403 MEMO ...