115
Motor brake and stop operation
4
(1) When the brake unit (FR-BU2, BU, FR-BU) is used
⋅
Set "0 (initial value), 10, 20, 100 or 120" in
Pr. 30
. The
Pr. 70
setting is invalid.
(2) When using a brake unit (MT-BU5) and power regeneration converter (MT-RC) (FR-F720-
03160 (FR-F740-01800) or more)
⋅
Set "1, 11, 21, 101 or 121" in
Pr. 30
.
⋅
Set "10%" In
Pr. 70
when using a brake unit (MT-BU5).
⋅
Set "0%" in
Pr. 70
when using a power regeneration converter (MT-RC).
(3) When using the high power factor converter (FR-HC, MT-HC) or power regeneration
common converter (FR-CV)
⋅
Set "2" in
Pr. 30
. The
Pr. 70
setting is invalid.
⋅
Use any of
Pr. 178 to Pr. 189 (Input terminal function assignment)
to assign the following signals to the contact input
terminals.
(a) X10 signal: FR-HC, MT-HC connection, FR-CV connection (inverter operation enable signal)
To make protective coordination with the FR-HC, MT-HC or FR-CV, use the inverter operation enable signal
to shut off the inverter output. Input the RDY signal of the FR-HC, MT-HC (RDYB signal of the FR-CV).
(b) X11 signal: FR-HC, MT-HC connection (instantaneous power failure detection signal)
When the setting has been made to hold the mode at occurrence of an instantaneous power failure for RS-
485 communication operation, use this signal to hold the mode. Input the Y1 or Y2 signal (instantaneous
power failure detection signal) of the FR-HC, MT-HC.
⋅
For the terminal used for X10 or X11 signal input, assign its function by setting "10" (X10) or "11" (X11) in any of
Pr.
178 to Pr. 189
.
(4) DC feeding mode 1 (
Pr. 30
= "10, 11")
⋅
Setting "10, 11" in
Pr. 30
enables DC power supply operation.
⋅
Leave the AC power supply connection terminal R/L1, S/L2, and T/L3 open and connect the DC power supply to
terminal P/+ and N/-. Also, remove jumpers across terminal R/L1 and R1/L11 as well as S/L2 and S1/L21, and
connect terminals R1/L11 and S1/L21 to terminal P/+ and N/-.
⋅
The diagram below is a connection example.
CAUTION
⋅
Set "1" in
Pr. 0 Brake mode selection
of the FR-BU2 to use GRZG type discharging resistor.
⋅
Do not operate the MT-BU5 type brake unit and FR-BU2 in parallel. Doing so could cause an alarm or brake unit failure. Use the
FR-BU2 only when performing parallel operation.
CAUTION
⋅
Set "2" in
Pr. 0 Brake mode selection
of the FR-BU2 to use MT-BR5 type resistor unit.
REMARKS
⋅
When
Pr. 30
= "2", "Err" is displayed on the operation panel as the inverter is reset by the setting.
R/L1
S/L2
T/L3
U
V
W
P/+
N/-
IM
STF
STR
R1/L11
S1/L21
10
2
2
3
1
5
(+)
(-)
MC
Inrush
current
limit circuit
DC power
Forward rotation start
Reverse rotation start
Contact input common
Frequency command
Frequency setting
potentiometer
1/2W1k
Ω
Earth
(Ground)
Inverter
SD