4
Inverter and peripheral devices
1.2.1
Peripheral devices
Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according
to the capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor
Output
(kW(HP))
*1
Applicable Inverter
Model
Breaker Selection
Input Side Magnetic Contactor
*3
Power factor improving
(AC or DC) reactor
Power factor improving
(AC or DC) reactor
Without
with
Without
with
0.75 (1)
FR-F720-00046-NA
10A
10A
S-N10
S-N10
1.5 (2)
FR-F720-00077-NA
15A
15A
S-N10
S-N10
2.2 (3)
FR-F720-00105-NA
20A
15A
S-N10
S-N10
3.7 (5)
FR-F720-00167-NA
30A
30A
S-N20, S-N21
S-N10
5.5 (7.5)
FR-F720-00250-NA
50A
40A
S-N25
S-N20, S-N21
7.5 (10)
FR-F720-00340-NA
60A
50A
S-N25
S-N25
11 (15)
FR-F720-00490-NA
75A
75A
S-N35
S-N35
15 (20)
FR-F720-00630-NA
125A
100A
S-N50
S-N50
18.5 (25)
FR-F720-00770-NA
150A
125A
S-N65
S-N50
22 (30)
FR-F720-00930-NA
175A
150A
S-N80
S-N65
30 (40)
FR-F720-01250-NA
225A
175A
S-N95
S-N80
37 (50)
FR-F720-01540-NA
250A
225A
S-N150
S-N125
45 (60)
FR-F720-01870-NA
300A
300A
S-N180
S-N150
55 (75)
FR-F720-02330-NA
400A
350A
S-N220
S-N180
75 (100)
FR-F720-03160-NA
⎯
400A
⎯
S-N300
90 (125)
FR-F720-03800-NA
⎯
400A
⎯
S-N300
110 (150)
FR-F720-04750-NA
⎯
500A
⎯
S-N400
*1
Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200VAC 50Hz.
*2
Select the MCCB according to the power supply capacity.
Install one MCCB per inverter.
For using commercial-power supply operation, select a breaker with capacity which allows the motor to be
directly power supplied.
For the use in the United States or Canada, provide the appropriate UL and cUL listed Class RK5, Class T
or Class L type fuse or UL 489 molded case circuit breaker (MCCB) that is suitable for branch circuit
protection.
(Refer to the Installation Guideline.)
*3
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the
MC with class AC-3 rated current for the motor rated current.
CAUTION
⋅
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model and cable and reactor according to the motor output.
⋅
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power ON the breaker.
MCCB
INV
MCCB
INV
IM
IM