220
Communication operation and setting
(3) Communication operation presence/absence and data format types
⋅
Data communication between the computer and inverter is made in ASCII code (hexadecimal code).
⋅
Communication operation presence/absence and data format types are as follows:
Data writing format
Communication request data from the computer to the inverter 1)
Reply data from the inverter to the computer 3) (No data error detected)
Reply data from the inverter to the computer 3) (With data error)
Symbol
Operation
Run
Command
Running
Frequency
Multi
command
Parameter
Write
Inverter
Reset
Monitor
Parameter
Read
1)
Communication request is sent to the
inverter in accordance with the user
program in the computer.
A, A1
A
A2
A
A
B
B
2)
Inverter data processing time
Present
Present
Present
Present
Absent
Present
Present
3)
Reply data from the
inverter (Data 1) is
checked for error)
No error
*1
(Request accepted)
C
C
C1
*3
C
C
*2
E, E1,
E2, E3
E
With error.
(Request rejected)
D
D
D
D
D
*2
D
D
4)
Computer processing delay time
10ms or more
5)
Answer from
computer in response
to reply data 3)
(Data 3) is checked
for error)
No error
*1
(No inverter
processing)
Absent
Absent
Absent
(C)
Absent
Absent
Absent
(C)
Absent (C)
With error
(Inverter re-
outputs 3))
Absent
Absent
F
Absent
Absent
F
F
*1
In the communication request data from the computer to the inverter, 10ms or more is also required after "no data error (ACK)".
*2
The inverter response to the inverter reset request can be selected.
*3
At mode error, and data range error, C1 data contains an error code.
Except for those errors, the error is returned with data
format D.
Format
Number of Characters
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
A
ENQ
Inverter
station
number *2
Instruction
code
Data
Sum
check
A1
ENQ
Inverter
station
number *2
Instruction
code
Data
Sum
check
A2
ENQ
Inverter
station
number *2
Instruction
code
Send
data
type
Receive
data
type
Data1
Data2
Sum
check
Format
Number of Characters
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
C
ACK
Inverter
station
number *2
C1
STX
Inverter
station
number *2
Send
data
type
Receive
data
type
Error
code 1
Error
code 2
Data1
Data2
ETX
Sum
check
Format
Number of Characters
1
2
3
4
5
D
NAK
Inverter
station
number *2
Error
code
*1
Indicate a control code
*2
Specify the inverter station numbers between H00 and H1F (stations 0 to 31) in hexadecimal.
*3
When
Pr.123
and
Pr.337
(Waiting time setting)
≠
9999, create a communication request data without "waiting time" in the data format. (The
number of characters decreases by 1.)
*4
CR, LF code
When data is transmitted from the computer to the inverter, codes CR (carriage return) and LF (line feed) are automatically set at the end of a
data group on some computers. In this case, setting must also be made on the inverter according to the computer. Whether the CR and LF
codes will be present or absent can be selected using
Pr. 124 PU communication CR/LF selection
.
Summary of Contents for 700 Series
Page 11: ...MEMO ...
Page 23: ...12 MEMO ...
Page 341: ...330 MEMO ...
Page 365: ...354 MEMO ...
Page 379: ...368 MEMO ...
Page 397: ...386 MEMO ...
Page 414: ...403 MEMO ...