Misoperation prevention and parameter
(3) Parameter operation during password lock/unlock
*1
Reading/writing is unavailable when there is restriction to reading by the
Pr. 160
setting. (Reading is available in NET mode regardless of
Pr. 160
setting.)
*2
Unavailable during the operation.
*3
Correct password will not unlock the restriction.
*4
Parameter clear is available only from the communication option.
Parameter operation
Unlocked
Password registered
Locked
Pr. 296
= 9999
Pr. 297
= 9999
Pr. 296
≠
9999
Pr. 297
= 9999
Pr. 296
≠
9999
Pr. 297
= 0 to 4
(Read value)
Pr. 296
= 100 to 106, 199
Pr. 297
= 5
(Read value)
Pr. 296
Read
Write
×
×
Pr. 297
Read
Write
×
Performing parameter clear
×
×
Performing parameter all clear
Performing parameter copy
×
×
: enabled,
×
: restricted
REMARKS
⋅
When
Pr. 296
= any of "4, 5, 104, 105" (password lock), the setting screen for PU JOG frequency is not displayed in the
parameter unit (FR-PU04/FR-PU07).
⋅
During password lock, parameter copy of the operation panel (FR-DU07)/the parameter unit (FR-PU07) cannot be performed.
⋅
Parameter settings in the inverter can be read/written using GX Developer even when the password function
(Pr.296, Pr.297)
is
valid. To use the password function and the PLC function at the same time, apply a lock to reading/writing of the ladder program
by registering a keyword.
♦
Parameters referred to
♦
Pr. 77 Parameter write selection
Pr. 160 Extended function display selection
Pr. 550 NET mode operation command source selection
Pr. 551 PU mode operation command source selection