255
Communication operation and setting
4
(7) Mailbox parameter/Mailbox value
Access to the properties which are not defined as objects are available by using "Mailbox parameter" and "Mailbox
value".
To read a property, write the register of the intended property to "Mailbox parameter", and then read "Mailbox value".
To write a property, write the register of the intended property to "Mailbox parameter", and then write a value to
"Mailbox value".
BACnet registers
System environment variable
Real-time monitor
for details of the monitor description.
*1
The setting depends on capacities. (FR-F720-02330 (FR-F740-01160) or less/FR-F720-03160 (FR-F740-01800) or more)
*2
Input terminal monitor details
*3
Output terminal monitor details
*4
When
Pr.37
= "1 to 9998" or
Pr. 144
= "2 to 10, 102 to 110," the unit is an integral value (one increment).
)
*5
Option input terminal 1 monitor details (input terminal status of FR-A7AX) All OFF if option is not installed.
*6
Option input terminal 2 monitor details (input terminal status of FR-A7AX) All OFF if option is not installed.
*7
Option output terminal monitor details (output terminal status of FR-A7AY) All OFF if option is not installed.
Register
Definition
Read/Write
Remarks
40010
Operation mode/
inverter setting
Read/write
For write, set data as the operation mode setting. For read,
data is read as the operation mode status.
*
Writing is available depending on the
Pr. 79
and
Pr. 340
settings.
for details.
The restrictions depending on the operation mode changes
according to the computer link specifications.
b15
b0
⎯
⎯
⎯
⎯
CS
RES
STOP
MRS
JOG
RH
RM
RL
RT
AU
STR
STF
b15
b0
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
ABC2
ABC1
FU
OL
IPF
SU
RUN
b15
b0
X15
X14
X13
X12
X11
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
X0
b15
b0
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
DY
b15
b0
⎯
⎯
⎯
⎯
⎯
⎯
RA3
RA2
RA1
Y6
Y5
Y4
Y3
Y2
Y1
Y0
Mode
Read Value
Written Value
EXT
H0000
H0010 *
PU
H0001
H0011 *
EXT JOG
H0002
⎯
PU JOG
H0003
⎯
NET
H0004
H0014
PU+EXT
H0005
⎯
Register
Description
Increments
40201
Output frequency/Speed
0.01Hz/1
40202
Output current
0.01A/0.1A
40203
Output voltage
0.1V
40205
Frequency setting value/Speed
setting
0.01Hz/1
40206
Running speed
1r/min
40208
Converter output voltage
0.1V
40209
Regenerative brake duty
0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211
Output current peak value
0.01A/0.1A
40212
Converter output voltage peak value
0.1V
40213
Input power
0.01kW/0.1kW
40214
Output power
0.01kW/0.1kW
40215
Input terminal status
⎯
40216
Output terminal status
⎯
40217
Load meter
0.1%
40220
Cumulative energization time
1h
40223
Actual operation time
1h
40224
Motor load factor
0.1%
40225
Cumulative power
1kWh
40250
Power saving effect
Variable
40251
Cumulative saving power
Variable
40252
PID set point
0.1%
40253
PID measured value
0.1%
40254
PID deviation
0.1%
40258
Option input terminal status 1
⎯
40259
Option input terminal status 2
⎯
40260
Option output terminal status
⎯
40267
PID measured value 2
0.1%
40277
32-bit cumulative power
(lower 16-bit)
1kWh
40278
32-bit cumulative power
(upper 16-bit)
1kWh
40279
32-bit cumulative power
(lower 16-bit)
0.01kWh/
0.1kWh
40280
32-bit cumulative power
(upper 16-bit)
0.01kWh/
0.1kWh
Register
Description
Increments
Summary of Contents for 700 Series
Page 11: ...MEMO ...
Page 23: ...12 MEMO ...
Page 341: ...330 MEMO ...
Page 365: ...354 MEMO ...
Page 379: ...368 MEMO ...
Page 397: ...386 MEMO ...
Page 414: ...403 MEMO ...