129
Function assignment of external
terminal and control
4
12
112
Y12
Output current
detection
Output when the output current is higher
than the
Pr. 150
setting for longer than the
time set in
Pr. 151
.
Pr. 150, Pr. 151
13
113
Y13
Zero current
detection
Output when the output power is lower than
the
Pr. 152
setting for longer than the time
set in
Pr. 153
.
Pr. 152, Pr. 153
14
114
FDN
PID lower limit
Output when the feedback value falls below
the lower limit of PID control.
Pr. 127 to Pr. 134,
Pr. 575 to Pr. 577
15
115
FUP
PID upper limit
Output when the feedback value rises above
the upper limit of PID control
16
116
RL
PID forward/reverse
rotation output
Output when forward rotation is performed in
PID control.
17
⎯
MC1
Electronic bypass MC1
Used when the bypass-inverter switchover
function is used.
Pr. 135 to Pr. 139,
Pr. 159
18
⎯
MC2
Electronic bypass MC2
19
⎯
MC3
Electronic bypass MC3
25
125
FAN
Fan fault output
Output at the time of a fan alarm.
Pr. 244
26
126
FIN
Heatsink overheat
pre-alarm
Output when the heatsink temperature
reaches about 85% of the heatsink overheat
protection operation temperature.
⎯
45
145
RUN3
Inverter running and
start command is ON
Output when the inverter is running and start
command is ON.
⎯
46
146
Y46
During deceleration at
occurrence of power
failure
Output when the power failure-time
deceleration function is executed.
(retained until release)
Pr. 261 to Pr. 266
47
147
PID
During PID control
activated
Output during PID control.
Pr. 127 to Pr. 134,
Pr. 575 to Pr. 577
48
148
Y48
PID deviation limit
Output when the absolute value of deviation
exceeds the limit value.
Pr. 127 to Pr. 134,
Pr. 241, Pr. 553, Pr.
554, Pr. 575 to Pr.
577, C42 to C45
49
149
Y49
During pre-charge
operation
Output during the pre-charge operation.
Pr. 127 to Pr. 134,
Pr. 241, Pr. 553,
Pr. 554,
Pr. 575 to Pr. 577,
Pr. 753 to Pr. 769,
C42 to C45
50
150
Y50
During second pre-
charge operation
51
151
Y51
Pre-charge time over
Output when the pre-charged time exceeds
the time set in
Pr.764
or
Pr.769
.
52
152
Y52
Second pre-charge
time over
53
153
Y53
Pre-charge level over
Output when the pre-charged amount
exceeds the set level in
Pr.763
or
Pr.768
.
54
154
Y54
Second pre-charge
level over
64
164
Y64
During retry
Output during retry processing.
Pr. 65 to Pr. 69
67
167
Y67
During power failure
Output during output shutoff due to power
failure or under voltage.
Pr. 57
70
170
SLEEP
PID output
interruption
Output when the PID output interruption
function is executed.
Pr. 127 to Pr. 134,
Pr. 575 to Pr. 577
Setting
Signal
Name
Function
Operation
Related
Parameters
Refer
to Page
Positive
Logic
Negative
Logic