345
Causes and corrective actions
5
Operation Panel
Indication
E.SER
FR-PU04
Fault 14
FR-PU07(-01) VFD Comm error
Name
Communication fault (inverter)
Description
This function stops the inverter output when communication error occurs consecutively for more than
permissible retry count when a value other than "9999" is set in
Pr. 335 RS-485 communication retry count
during RS-485 communication from the RS-485 terminals. This function also stops the inverter output if
communication is broken for the period of time set in
Pr. 336 RS-485 communication check time interval
.
Check point
Check the RS-485 terminal wiring.
Corrective action
Perform wiring of the RS-485 terminals properly.
Operation Panel
Indication
E.AIE
FR-PU04
Fault 14
FR-PU07(-01) Analog in error
Name
Analog input fault
Description
Stops the inverter output when 30mA or higher current is input to terminal 2 or 4 while current input is
selected with
Pr. 73 Analog input selection
or
Pr. 267 Terminal 4 input selection
. The function also stops the
inverter output when voltage (7.5V or higher) is input.
Check point
Check the setting of
Pr. 73 Analog input selection
and
Pr. 267 Terminal 4 input selection
.
(Refer to page 171.)
Corrective action
Either give a frequency command by current input or set
Pr. 73 Analog input selection
or
Pr. 267 Terminal
4 input selection
to voltage input.
Operation Panel
Indication
E.PID
FR-PU04
Fault 14
FR-PU07
Fault
FR-PU07-01
PID Signal Error
Name
PID signal fault
Description
If any of PID upper limit (FUP), PID lower limit (FDN), and PID deviation limit (Y48) turns ON during PID
control, inverter shuts off the output. This function is active under the following parameter settings:
Pr.554 PID
signal operation selection
≠
"0,10",
Pr.131 PID upper limit
≠
"9999",
Pr.132 PID lower limit
≠
"9999", and
Pr.553 PID
deviation limit
≠
"9999". This protective function is not active in the initial setting (
Pr.554
= "0",
Pr.131
= "9999",
Pr.132
= "9999",
Pr.553
= "9999").
Check Point
Check if the measured PID value is greater than the upper limit
(Pr.131)
or smaller than the lower limit
(Pr.132)
.
Check if the absolute PID deviation value is greater than the limit value
(Pr.553)
.
Corrective Action
Make correct settings for
Pr.131 PID upper limit
,
Pr.132 PID lower limit
,
Pr.553 PID deviation limit
.
(Refer to page
Operation Panel
Indication
E.13
FR-PU04
FR-PU07(-01)
Fault 13
Name
Internal circuit fault
Description
Trips when an internal circuit error occurred.
Corrective action
Please contact your sales representative.
Operation Panel
Indication
E.PCH
FR-PU04
Fault 14
FR-PU07
Fault
FR-PU07-01
Precharge Error
Name
Pre-charge fault
Description
When the pre-charged time exceeds the
Pr.764 (Pr.769)
Pre-charge time limit
, or the pre-charged amount
exceeds
Pr. 763 (Pr. 768)
Pre-charge upper detection level
, the protective circuit activates, and the inverter
output is shutoff. This function is available when
Pr.764 (Pr.769)
Pre-charge time limit
or
Pr. 763 (Pr. 768)
Pre-charge upper detection level
is set. This protective function is not available in the initial status.
(Refer
to page 261)
Check point
· Check if the
Pr.764 (Pr.769)
Pre-charge time limit
setting is too low.
· Check if the
Pr. 763 (Pr. 768)
Pre-charge upper detection level
setting is too low.
· Check if the automatic switchover frequency set in
Pr.127 (Pr.754)
is too low.
· Check if there is a break in the connection with a pump.
Corrective action
· Set the
Pr.764 (Pr.769)
Pre-charge time limit
setting higher.
· Set the
Pr. 763 (Pr. 768)
Pre-charge upper detection level
setting higher.
· Set the automatic switchover frequency higher in
Pr.127 (Pr.754)
.
· Check the connection with a pump.