Monitor display and monitor output signal
4
4.11 Monitor display and monitor output signal
4.11.1 Speed display and speed setting (Pr. 37, Pr. 144, Pr. 505)
...... The specification differs according to the manufacture date. Refer to
page 400
and check the SERIAL.
*1
The maximum value of the setting range differs according to the
Pr.1 Maximum frequency
and it can be calculated from the following formula.
Note that
Pr.37
(set maximum value) is 9998 if the result of the above formula exceeds 9998.
*2
The above parameters can be set when
Pr. 160 User group read selection
= "0".
(Refer to page 190)
⋅
To display the machine speed, set in
Pr. 37
the machine speed for operation with frequency set in
Pr. 505
.
For example, when
Pr. 505
= "60Hz" and
Pr. 37
= "1000", "1000" is displayed on the running speed monitor when the
running frequency is 60Hz. When running frequency is 30Hz, "500" is displayed.
⋅
When displaying the motor speed, set the number of motor poles (2, 4, 6, 8, 10) or number of motor poles + 100
(102, 104, 106, 108, 110) to
Pr. 144
.
⋅
When both
Pr. 37
and
Pr. 144
have been set, their priorities are as given below.
Pr. 144
, 102 to 110
>
Pr. 37
, 1 to 9998
>
Pr. 144
, 2 to 10
⋅
When the running speed monitor is selected, each monitor and setting are determined by the combination of
Pr. 37
and
Pr. 144
as listed below. (The units within the thick frame are the initial values.)
Purpose
Parameter that must be set
Refer to
Page
Display motor speed
Set speed
Speed display and speed setting
Pr. 37, Pr. 144, Pr. 505
Change PU monitor display data
DU/PU main display data selection
Cumulative monitor clear
Pr. 52, Pr. 170, Pr. 171,
Pr. 268, Pr. 891
Change of the monitor output from
terminal CA and AM
Terminal CA, AM function selection
Pr. 54, Pr. 158, Pr. 867, Pr. 869
Set the reference of the monitor
output from terminal CA and AM
Setting of reference of terminal CA and AM
Pr. 55, Pr. 56, Pr. 867
Adjust terminal CA, AM outputs
Terminal CA, AM calibration
Pr. 900, Pr. 901, Pr. 930, Pr. 931
You can change the PU (FR-DU07/FR-PU04/FR-PU07) monitor display or frequency setting to motor speed or
machine speed.
Parameter
Number
Name
Initial Value
Setting Range
Description
37
Speed display
0
0
Frequency display, setting
1 to 9998
*1
Set the machine speed at 60Hz.
144
Speed setting switchover
4
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
Set the number of motor poles when
displaying the motor speed.
505
Speed setting reference
60Hz
1 to 120Hz
Set the reference speed for
Pr. 37
.
Pr.37
(set maximum value)
<
65535 x
Pr.505
Pr.1
(Hz)
Pr. 37
Setting
Pr. 144
Setting
Output Frequency
Monitor
Set Frequency
Monitor
Running Speed
Monitor
Frequency Setting
Parameter Setting
0
(initial
value)
0
Hz
Hz
r/min
Hz
2 to 10
Hz
Hz
r/min
Hz
102 to 110
r/min
r/min
r/min
r/min
1 to 9998
0
Hz
Hz
Machine speed
Hz
2 to 10
Machine speed
Machine speed
Machine speed
Machine speed
102 to 110
Hz
Hz
r/min
Hz
*1
Motor speed r/min conversion formula............ frequency
×
120/number of motor poles (
Pr. 144
)
Machine speed conversion formula
...................Pr. 37
×
frequency/
Pr. 505
setting (Hz)
For
Pr. 144
in the above formula, the value is "
Pr. 144
-100" when "102 to 110" is set in
Pr. 144
and the value is "4" when
Pr. 37
= 0 and
Pr. 144
= 0.
*2
The increments for Hz are 0.01Hz, machine speed are 1m/min, and r/min are 1r/min.
*3
Pr. 505
is always set as frequency (Hz).