5
Inverter and peripheral devices
400V class
Motor
Output
(kW(HP))
Applicable Inverter Model
Breaker Selection
Input Side Magnetic Contactor
*3
Power factor improving
(AC or DC) reactor
Power factor improving
(AC or DC) reactor
Without
with
Without
with
0.75 (1)
FR-F740-00023-NA
5A
5A
S-N10
S-N10
1.5 (2)
FR-F740-00038-NA
10A
10A
S-N10
S-N10
2.2 (3)
FR-F740-00052-NA
10A
10A
S-N10
S-N10
3.7 (5)
FR-F740-00083-NA
20A
15A
S-N10
S-N10
5.5 (7.5)
FR-F740-00126-NA
30A
20A
S-N20, S-N21
S-N11, S-N12
7.5 (10)
FR-F740-00170-NA
30A
30A
S-N20, S-N21
S-N20, S-N21
11 (15)
FR-F740-00250-NA
50A
40A
S-N20, S-N21
S-N20, S-N21
15 (20)
FR-F740-00310-NA
60A
50A
S-N25
S-N20, S-N21
18.5 (25)
FR-F740-00380-NA
75A
60A
S-N25
S-N25
22 (30)
FR-F740-00470-NA
100A
75A
S-N35
S-N25
30 (40)
FR-F740-00620-NA
125A
100A
S-N50
S-N50
37 (50)
FR-F740-00770-NA
150A
125A
S-N65
S-N50
45 (60)
FR-F740-00930-NA
175A
150A
S-N80
S-N65
55 (75)
FR-F740-01160-NA
200A
175A
S-N80
S-N80
75 (100)
FR-F740-01800-NA
⎯
225A
⎯
S-N95
90 (125)
FR-F740-01800-NA
⎯
225A
⎯
S-N150
110 (150)
FR-F740-02160-NA
⎯
225A
⎯
S-N180
132 (200)
FR-F740-02600-NA
⎯
400A
⎯
S-N220
160 (250)
FR-F740-03250-NA
⎯
400A
⎯
S-N300
185 (300)
FR-F740-03610-NA
⎯
400A
⎯
S-N300
220 (350)
FR-F740-04320-NA
⎯
500A
⎯
S-N400
250 (400)
FR-F740-04810-NA
⎯
600A
⎯
S-N600
280 (450)
FR-F740-05470-NA
⎯
600A
⎯
S-N600
315 (500)
FR-F740-06100-NA
⎯
700A
⎯
S-N600
355 (550)
FR-F740-06830-NA
⎯
800A
⎯
S-N600
400 (600)
FR-F740-07700-NA
⎯
900A
⎯
S-N800
450 (700)
FR-F740-08660-NA
⎯
1000A
⎯
1000A
Rated product
500 (750)
FR-F740-09620-NA
⎯
1200A
⎯
1000A
Rated product
560 (800)
FR-F740-10940-NA
⎯
1500A
⎯
1200A
Rated product
630 (850)
FR-F740-12120-NA
⎯
2000A
⎯
1400A
Rated product
*1
Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 400VAC 50Hz.
*2
Select the MCCB according to the power supply capacity.
Install one MCCB per inverter.
For using commercial-power supply operation, select a breaker with capacity which allows the motor to be
directly power supplied.
For the use in the United States or Canada, provide the appropriate UL and cUL listed Class RK5, Class T
or Class L type fuse or UL 489 molded case circuit breaker (MCCB) that is suitable for branch circuit
protection.
(Refer to the Installation Guideline.)
*3
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the
MC with class AC-3 rated current for the motor rated current.
CAUTION
⋅
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model and cable and reactor according to the motor output.
⋅
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power ON the breaker.
MCCB
INV
MCCB
INV
IM
IM
Summary of Contents for 700 Series
Page 11: ...MEMO ...
Page 23: ...12 MEMO ...
Page 341: ...330 MEMO ...
Page 365: ...354 MEMO ...
Page 379: ...368 MEMO ...
Page 397: ...386 MEMO ...
Page 414: ...403 MEMO ...