Setting of FR-PU07-01
4.24.4 3-line monitor selection (Pr. 774 to Pr.776)
*1
The monitor is displayed as
Pr. 774
= "1,"
Pr. 775
= "2," and
Pr. 776
= "3" when a parameter unit other than FR-DU07 is used.
*2
The monitor is displayed as
Pr. 774
= "1,"
Pr. 775
= "2," and
Pr. 776
= "3" when the monitor selection is valid.
*3
The setting is available when using PLC function. Refer to the FR-F700 PLC function programming manual for details of the PLC function.
For the parameter unit (FR-PU07)/operation panel (FR-DU07), the first, second, and third monitors can be
changed. When using FR-PU07-01, the monitored items, which are set by
Pr.774 to Pr.776
, can be displayed in
the 3-line monitor.
The
Pr.52 DU/PU main display data selection
setting is invalid when
Pr.774 to Pr.776
≠
9999. Monitored item names
are displayed during monitoring (Monitor name display in the 3-line monitor is available only for FR-PU07-01).
Parameter
Number
Name
Initial
Value
Setting
Range
Description
774
PU/DU monitor
selection 1
9999
1 to 3, 5, 6, 8 to
14, 17, 20,
23 to 25, 40 to
42, 50 to 57,
67, 81 to 86,
100, 9999
Select the monitored item to be displayed on the first monitor
(first row in the 3-line monitor).
775
PU/DU monitor
selection 2
Select the monitored item to be displayed on the second
monitor (second row in the 3-line monitor).
776
PU/DU monitor
selection 3
Select the monitored item to be displayed on the third monitor
(third row in the 3-line monitor).
♦
Parameters referred to
♦
Pr. 52 DU/PU main display data selection
Pr. 59 Remote function selection
Pr. 73 Analog input selection
Pr. 79 Operation mode selection
Pr. 133 PID action set point
Pr. 160 User group read selection
Pr. 178 to Pr. 189 (input terminal function selection)
Pr. 190 to Pr. 196 (output terminal function selection)
C2 (Pr. 902) to C7 (Pr. 905) Frequency setting voltage (current) bias/gain
C42 (Pr. 934) to C45 (Pr. 935) (PID control)
Setting
Monitor item
1
Output frequency
2
Output current
3
Output voltage
5
Frequency setting value
6
Running speed
8
Converter output voltage
9
Regenerative brake duty
10
Electronic thermal relay
function load factor
11
Output current peak value
12
Converter output voltage peak
value
13
Input power
14
Output power
17
Load meter
20
Cumulative energization time
23
Actual operation time
24
Motor load factor
25
Cumulative power
40
PLC function user monitor 1
*3
41
PLC function user monitor 2
*3
42
PLC function user monitor 3
*3
50
Power saving effect
51
Cumulative saving power
52
PID set point
53
PID measured value
54
PID deviation
55
*1
I/O terminal status
56
*1
Option input terminal status
57
*1
Option output terminal status
67
PID measured value 2
81
BACnet reception status
82
BACnet token pass counter
83
BACnet valid APDU counter
Setting
Monitor item
84
BACnet communication error
counter
85
Terminal CA output level
86
Terminal AM output level
100
Set frequency before
operation
9999
*2
No selection
Setting
Monitor item
How the monitor is displayed when
Pr. 759
= "4,"
Pr. 774
= "52,"
Pr. 775
= "53,"
and
Pr. 776
= "54"
2 + & U G V 2 5 +
2 + & X C N 2 5 +
2 + & F G X 2 5 +
5 6 ( ( 9 & * # 0 &